Specifications

1-2 ELECTRICAL SPECIFICATIONS

Power Supply
Name
Phase
Frequency
Voltage
Current
Minimum circuit amps
(MCA)
Maximum fuse amps (MFA) A
Full load amps (FLA)
Voltage range
Minimum
Maximum
Notes
• Indoor Units • CONCEALED CEILING UNIT • FXMQ-PVE
FXMQ40PVE
FXMQ50PVE
Hz
V
A
1.4
16
A
1.1
V
V
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below
Maximum allowable voltage range variation between phases is 2%.
®
• VRV
Systems • Indoor Units
FXMQ63PVE
FXMQ80PVE
VE
1~
50/60
220-240/220
1.6
1.8
16
16
1.3
1.4
-10%
+10%
or above listed range limits.
MCA/MFA : MCA = 1.25 x FLA
MFA is smaller than or equal to 4 x FLA
Next lower standard fuse rating minimum 16A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker
FXMQ100PVE
FXMQ125PVE
2.3
2.9
16
16
1.8
2.3
3.4
16
2.7