3.4) Fuse and overload protection
Fuse ratings and type – industrial cylindrical cartridge
90 to 280kW
F1 – 1A type aM, F2 – 1A type gG, F3 – 0.5A type gG
315 to 630kW
F1 – 1A type aM, F2 – 1A type gG, F3 – 0.5A type gG
F4 – F6 type 22 x 58 : 63A type gG
Type 0 : 125A type gG
Type 1 : 160A type gG
Type 2 : 250, 315 & 400A type gG
Amperage requirement – insert table from earlier
ELECTRICAL CIRCUIT
The Standard electric boiler must be provided with 415volts and
without neutral wiring
The electrical wiring cables must be sized by a qualified electrician in
order to conform
to BS C 15100 and satisfying load, length of run and prevention of short
circuit.
The installation must be tested for automatic power failure in the
event of emergency
power cut, heater lock-out or error in the neutral layout.
All electrical equipment shall satisfy IP21/IK08 Class 1
The immersion heaters shall only receive electrical power if they are
fully immersed in water; otherwise the guarantee on the heaters will
not apply
ALL ELECTRICAL WIRING MUST BE CORRECTLY EARTHED
11