Anly AT02 Series User Manual
Browse online or download pdf User Manual for Temperature Controller Anly AT02 Series. Anly AT02 Series 2 pages.
AT02
SERIES PID
TEMPERATURE CONTROLLER
User's Manual
RESTRICTIONS ON USE
When using this product in applications
that require particular safety or when
using this product in important facilities,
please pay attention to the safety of the
overall system and equipment. Install fail-
safe mechanisms, perform redundancy
checks and periodic inspections and
adopt other appropriate safety measures
when it is necessary.
ATTENTION !
1.Please read the SAFETY PRECAUTION
section on reverse side before use of
this product.
2.Please read this user's manual before
use for proper operation.
3.Please safe guard this user's manual.
Function Setting
Warning! Please make sure the power is off, before
making any changes on the DIP switch.
ON
1
2
3
4
5
6
K Type
0~1200
C
O
J Type
0~500
C
O
Input type
R Type
0~1700
O
C
PT-100
-50~400
C
O
ON/OFF CONTROL
Control Mode
PID CONTROL
RELAY
Output
DC 24V
(for SSR driven)
List of Alarm Mode :
1
Deviation High Alarm
2
Deviation Low Alarm
3
Process High Alarm
4
Process Low Alarm
5
Deviation High/Low Alarm
6
Band Alarm
7
Deviation High Alarm
(Standby)
8
Deviation Low Alarm
(Standby)
9
Process High Alarm
(Standby)
1 0
Process Low Alarm
(Standby)
11
Deviation High/Low Alarm
(Standby)
1 2
Band Alarm
(Standby)
Key Lock Setting
Under uSr level, press key for 3
seconds to enter Key Lock mode.
o
C
PV
Set Lock mumber according to
the level of protection.
SV
AT
OUT
ALM
LOCK
List of Key Lock Mode :
u s r P i d S E t A r G
Others
0 0 2 2
0 111
11 2 2
Symbol
: Can display and can be set
: Can't display nor can't be set
LEDs
AT: Lit when the auto
OUT: Lit when the control
ALM: Lit when the alarm
LOCK: Lit when the key
Key :
Switches the display. Hold
down for 3 seconds to
switch modes.
1
Power ON
DIP Switch
The initial screen
is displayed for
1
2
3
4
5
6
about 3 seconds.
ON
OFF
OFF
2
The IC version
ON
ON OFF
is displayed for
ON
OFF ON
about 6 seconds.
OFF
ON
ON
OFF
3
The operation
ON
mode is
OFF
displayed.
ON
4
Press
3 seconds to the
Alarm range
setting mode.
5
Press
once to the Auto
Tunning switch
mode
Press
6
once to the PV
Offset mode.
Press
7
once to the SV
Offset mode.
8
Press
once to the
operation mode.
PV
SV
AT
OUT
Names and Functions of Parts
PV
tuning is ON.
output is ON.
SV
output is ON.
AT
is locked.
SET
User Level Setting
o
C
PV
SV
AT
OUT
ALM
LOCK
o
C
PV
t ic
IC version
SV
AT
OUT
ALM
LOCK
o
C
PV
Current PV value
Current SV value
SV
AT
OUT
ALM
LOCK
key for
AS1:
o
C
PV
Alarm range setting
Temperature range
SV
varies with Input
AT
OUT
ALM
LOCK
type
key
At:
o
C
PV
Auto Tunning
YES / no
SV
AT
OUT
ALM
LOCK
key
PoF:
o
C
PV
PV Offset
-200.0~200.0
SV
AT
OUT
ALM
LOCK
key
SoF:
o
C
PV
SV Offset
-200.0~200.0
SV
AT
OUT
ALM
LOCK
key
o
C
PV
Current PV value
Current SV value
SV
AT
OUT
ALM
LOCK
SV Lock Setting
Under operation mode, press
o
C
key for 3 seconds to lock the SV
value.
And press
key for 3 seconds
again to unlock the SV value.
ALM
LOCK
AT-502
Upper Display
Displays PV values (current
o
C
temperature, etc.) or setup
items.
Lower Display
Displays SV values (set
temperature, etc.) and
OUT
ALM
LOCK
other parameter values.
Used to change numeric
values.
Used to shift setup items or
parameter digits.
PID Control Setting
Ensure the DIP switch is set to PID control mode before
proceed further.
1
Start with
operation mode.
PV
SV
AT
OUT
2
Press
key for
3 seconds to the
PV
parameter mode.
SV
AT
OUT
3
Press
key
once and
key
PV
once to the PID
level.
SV
AT
OUT
4
Press
key for
3 seconds to the
PV
P mode.
SV
AT
OUT
5
Press
key
once to the I
PV
mode.
SV
AT
OUT
O
C
6
Press
key
once to the D
PV
mode.
SV
AT
OUT
O
C
7
Press
key
once to the Relay
PV
output cycle
mode.
SV
AT
OUT
8
Press
key
once to the SSR
PV
output cycle
mode.
SV
AT
OUT
9
Press
key for
3 seconds to the
operation mode.
Key :
Key :
o
C
Current PV value
Current SV value
ALM
LOCK
o
C
LVL
uSr
ALM
LOCK
o
C
LVL
Pid
ALM
LOCK
P1:
o
C
Proportional band (P)
O
0.1~300.0
C
ALM
LOCK
i1:
o
C
Integral time (I)
0~7200sec
(Set 0 for P Control)
ALM
LOCK
d1:
o
C
Derivative time
(D)
0~1800sec
(Set 0 for P Control)
ALM
LOCK
Ct1:
o
C
Output cycle 1
0~65sec
ALM
LOCK
Ct2:
o
C
Output cycle 2
0~65sec
ALM
LOCK