Daikin RN50HV1A Service Manual Removal Procedure - Page 8
Browse online or download pdf Service Manual Removal Procedure for Fan Daikin RN50HV1A. Daikin RN50HV1A 15 pages. 5.0 kw class outdoor unit
Removal of Outdoor Fan / Fan Motor
Step
4
Cut the 3 clamps and
release the fan motor
lead wire.
5
Remove the nut and
remove the outdoor fan.
6
Remove the 4 screws
and remove the fan
motor.
6
Procedure
Put the fan motor lead wire
through the back of the fan
motor when reassembling so
as not to be entangled with
the outdoor fan.
Lead wire
(R5404)
Nut size: M6
D-cut
When reassembling, align
the
fan with the D-cut section of
the motor shaft.
(R5405)
Be sure to remove the lower
screws first. If the upper
screws are removed first, the
fan motor may tilt or fall
because the center of its
gravity is toward the front.
It may cause injuries.
(R5406)
Si011084
Points
Outdoor fan
(R3249)
10 mm
(R12236)
mark of the outdoor
Removal Procedure