DSC AMP-704 Installation Instructions - Page 2
Browse online or download pdf Installation Instructions for Control Unit DSC AMP-704. DSC AMP-704 4 pages. Point interface module
Wiring
Connect the AMP-704 wiring as indicated below:
Loop Current vs. Wiring Distance
(from PC4020/PC5100)
Total Loop
Current (mA)
distance (ft/m)
10
20
30
40
50
70
100
120
150
170
CAUTION: Connect only DSC addressable devices to the addressable loop
connections. Connection of any other type of device will impair operation. Any
devices other than addressable devices that require power to operate must be
powered separately.
Figure 3: Power Limited and Non-Power Limited Wiring
all compatible control panels)
NON-POWER
INSTALL BATTERY & AC WIRING AS SHOWN
IMPORTANT: A minimum 1/4" (6.4mm) separation must be main-
tained at all points between battery/primary AC wiring and all other
wiring connections. The AMP-704 is mounted inside the compatible
control unit's enclosure using 3 nylon spacers 3/8" (9.6mm).
22 AWG
18 AWG
distance (ft/m)
2880/878
5143/1568
1620/494
3645/1111
1010/308
2520/768
771/235
1736/529
600/183
1250/768
400/122
800/244
200/61
310/95
135/41
155/47
100/30
124/37
96/28
120/35
POWER
LIMITED
WARNING: Do not route any wiring
over circuit boards. Maintain at least
1" (25.4mm) separation.
Cable
Tie
Cable Tie (not provided)
Class2
To prevent wires from falling onto batteries,
Power
secure them to the enclosure or to the plastic
Limited
standoff located under the control panel.
37VA
Voltage
Barrier
LIMITED
Figure 2: AMP-704 Wiring
SUPERVISED,
POWER LIMITED
PC4020: PGM1/PGM2
PC5100: STR+
PC4020: AUX-
PC5100: STR-
(this diagram is representative of
Compatible
Control Panel
KEYBUS
Power Limited
Non-Power
Limited
-
-
+
+
7Ah
IN GND Z1 COM Z2
SUPERVISED,POWER LIMITED
Refer to EOL supervision
for proper input connections
Rating: 12V, 1mA
POWER
LIMITED
For fire installations,
lines come through
conduit connections.
7Ah
Z3 COM Z4