Power Supply Module
The PC5200 can be used to provide up to 1.0A of additional current to the
compatible DSC Alarm Controllers, models PC5010, PC5015, PC5020,
PC1864, PC1832 and PC1616. PC1616/1832/1864 v4.1 or higher sup-
ports up to four PC5200 modules.
This installation sheet shall be used with the Installation Manual of the DSC
equipment to which the PC5200 is connected or powered from (e.g. alarm
controller, power supply, etc.).
General
This product meets the requirements of Class II, Grade 2 equipment as per
EN50131-1:2006+A1:2009, EN50131-3:2009 Type B, EN50131-6:2008
Type A.
Specifications
• Power Supply Type A as per EN50131-6 Standard
• Temperature range: -10ºC to +55ºC
• Relative Humidity: 93% non condensing
• Input ratings: 220V-240Vac, 50/60Hz, 200mA
• Transformer required, mounted in the same enclosure and permanently
connected
NOTE: For installations using the transformer mounted inside the cabinet,
replace the fuse only with same type (20mm) rated 250V/315mA.
• Transformer secondary ratings: 16.5Vac, 40VA
• Board current draw: 20mA (set and unset state / alarm and non-alarm
state)
• Board dimensions: 145 mm x 83 mm
• AUX output ratings: 12V
, -15%/+15% when Input voltage is between
DC
85% to110% of rated value and output current is between 0.0A - 1.0A
max.
• Resettable fuse (PTC) used on circuit board instead of replaceable fuses
• Output ripple voltage: 600mVp-p max
• No Overvoltage protection devices required on the outputs
• Storage device: rechargeable battery, rated 12V
3-5 years
• Battery capacity: 4Ah, 7Ah or 14Ah (2 x 7Ah) max.
• Maximum standby time 24h (when using 14Ah battery capacity and AUX
current limited to 480mA max. Refer to Table 1
• Recharging time: up to 80% in less than 72h
• Low battery trouble indication threshold 11.5V
• Battery deep discharge protection (cut-off at 9.5V
NOTE: Main control panel and power supply shall be powered from the
same AC mains circuit. Deep discharge protection works only when there is
no voltage on the keybus connection.
NOTE: For EN50131-6:2008 compliant installations, use only one 12V/7Ah
battery for 12h of required standby time (550mA output current).
• Supervision for loss of primary power source (AC Fail) battery fail or bat-
tery low voltage (Battery Trouble) with indication provided on the keypad
Table 1
PC5200 Current
Draw 20mA
Max. Aux Current
Draw @12V
DC
Transformer
Requirements
Battery
Requirements
UL Listed
Enclosures
Standby Time (min.) 4 hours
Terminal Descriptions
NOTE: Devices that require
power from the PC5200 shall be
UL Listed for the intended
application and operate over the
range 11.5 - 12.5VDC.
Residential Fire Applications
For battery requirements and
standby time refer to Table 1.
Recommended Battery:
DSC model BD7-12.
AC - Supervised, the PC5200 requires a 16V/40VA transformer. Connect the
primary of the transformer to an unswitched AC source (maximum current
. Replace battery every
DC
draw is 0.5A) and connect the secondary of the transformer (US market
only) to these terminals.
AUX+ - This terminal is used to provide power for devices & modules.
Please refer to Table 1 for maximum ratings.
Connect the positive lead of powered devices to AUX and the negative to the
proper output terminal (O1 to O4).
DC
TAM - This can be used to tamper the cabinet in which the PC5200 is
)
DC
mounted. Connect a normally closed (NC) switch across TAM and BLK. If
the tamper is not being used connect a piece of wire across TAM and BLK to
remove the trouble condition.
Keybus- The 4-wire Keybus connection is used by the panel to communi-
cate with the module. Connect the RED, BLK, YEL & GRN terminals to the
RED, BLK, YEL & GRN Keybus terminals on the compatible control panel.
UL Residential
UL Commercial
EN50131
Burglary
Fire
Burglary
Grade 2 /Class 2
1A
550mA
1A
550mA
16.5V, 40VA
16V,
16V, 40VA
16V, 40VA
(Mounted inside
40VA
cabinet)
14Ah min
7Ah min
7Ah min
7Ah min
(2x7Ah)
PC5003C
CMC-1
PC5003C
PC500C
(Household Fire
PC4050CAR
PUC1
& Burglary)
24 hours
4 hours
12 hours
Residential
Burglary
Class 2
120VAC 60Hz
PRIMARY
RED
TRANSFORMER
BLK
AUX**
16VAC / 40VA PTD 1640
YEL
GRN
Enclosures
The PC5200 can be installed in the metal enclosures listed below:
• Model PC5003C (removable door) made of 22Ga steel, painted, dimen-
sions: 248mm(L) x 298mm(W) x 76mm(H), weight: 1500g.
• Model PC5003C (hinged door) made of 1.2mm thick steel, painted,
dimensions: 248mm(L) x 298mm(W) x 76mm(H), weight: 2500g
• Model Power UC1 made of 18Ga steel, painted, dimensions: 315mm(L) x
319mm(W) x 100mm(H), weight: 3150g.
• Model PC4003C made of 18Ga steel, painted, dimensions: 230mm(L) x
180mm(W) x 75mm(D), weight 1050g.
Tamper protection switches can be installed on all enclosures, including
door opening protection and/or removal from the mounting position. Doors
can be secured using screws or keylock. The PC5200 may be installed
within the same metallic cabinet as the alarm controller/power supply
(model Power UC1, PC5003C) or in a separate enclosure (model
PC4003C). Internal and/or external wiring for this module shall be routed,
supported, clamped or secured in a manner that reduces the likelihood of:
• excessive strain on wire and on terminal connections,
• loosening of terminal connections and
• damage of conductor insulation
NOTE: For EN50131-1 Grade 2 compliant installations, all unused holes on
the side of the cabinet must be covered (plugged). Also, the security tape
must be applied over the hinges of the removeable door in order to prevent
undetected access to the inside of the cabinet.
NOTE: The PC5200 power supply has been certified by Telefication accord-
ing to EN50131-1:2006 + A1:2009 and EN50131-6:2008, for Grade 2,
TO
Class II, Type A when installed in PC5003C (removable door) enclosure.
KEYBUS
BLK
PC5200 Jumper Settings
The PC5200 has 2 jumpers; to select which PC5200 slot is to be used refer
to the table below.
Table 2
SLOT
J1
PC5200 1
OFF
PC5200 2
ON
PC5200 3
OFF
PC5200 4
ON
J2
OFF
OFF
ON
ON