DSPM Power Lynx 1 Technical Specifications
Browse online or download pdf Technical Specifications for UPS DSPM Power Lynx 1. DSPM Power Lynx 1 10 pages.
Power Lynx 1
Uninterruptible Power System (UPS)
Technical Specifications
PART 1 GENERAL
1.1 SUMMARY
A. This specification describes a single phase, on-line, double conversion, solid state Uninter-
ruptible Power System utilizing Patented ECM Technology here after referred to as the UPS.
The UPS shall operate in conjunction with the existing electrical system to provide high quality
power conditioning, back-up power protection and distribution for Lighting loads and other
critical loads. T he system shall consist of a solid-state inverter, a temperature compensated
rectifier/battery charger, a 100% rated for continuous duty static switch, an internal maintenance
bypass switch, battery plant, status/control panel, and synchronizing circuitry. The enclosure is
a Nema 3R (outdoor) rain / weather resistant enclosure designed for outdoor environmental
conditions as described herein.
1.2 STANDARDS
A. The UPS shall meet the requirements of the following standards:
1. IEEE 587-1980/ANSI C62.41 1980 Standards for Surge Withstand
Ability
2. FCC rules and regulations of Part 15, Subpart J, Class A
3. Listed under UL 924, Standards for Lighting Inverter Equipment
4. NEMA PE 1 (National Electrical Manufacturers Association) -
Uninterruptible Power Systems
5. NEMA 250 (National Electrical Manufacturers Association) – Enclosures
for Electrical Equipment (1000 Volts Maximum)
6. NFPA 70 – National Electrical Code
7. ISO 1001
8. Occupational Safety & Health Administration (OSHA)
Title: Micro
01
Doc No.: 018-1000-02
Description: Emergency Lighting Inverter User's Manual
Phone :
Fax:
Rev: NR
Website:
Date: 07/26/2016
E-Mail:
1.877.DSPM.POWER
-
1.877.377.6769
909.930.3335
www.dspmanufacturing.com