Auber Instruments HD330 Instruction Manual - Page 2
Browse online or download pdf Instruction Manual for Controller Auber Instruments HD330. Auber Instruments HD330 5 pages. Dual output programmable humidity controller
AUBER INSTRUMENTS
about 3s. Then WIFI indicator will blink fast (4 Hz). This indicates that this
controller is waiting for new setup now. After the controller is setup to your
phone successfully, the WIFI indicator will be solid ON at most of the time.
4. Basic Operation
Here are the basic operating procedures to use this controller. To fully
understand the functions on this controller, please read the entire manual.
1) Connect the humidity sensor to the sensor socket that is located on the
bottom of the controller. Please check the alignment of the slot on the plug with
the key on the socket to ensure a connection. (See section 12 for details.)
2) Plug the controller's power cord to a wall outlet.
3) Set up the program and system parameters. (Please read the rest of this
manual for details.)
4) Connect the humidifying and dehumidifying devices to the output sockets on
this controller.
5) Press the START key to start running the program.
5. Mode Selection
This controller has 5 different modes: program run, program hold, program
stop, parameter setting, and programming mode. Before powering on the
controller, please connect the sensor cable to it. If no sensor is connected or if
sensor is failed, the controller will show error code "Err".
Programming
SET
Mode
Parameter
SET
2 s
Setting Mode
Figure 2. Switching between different modes.
Program Run: In this mode, the controller is executing the saved program.
The green indicator labeled "RUN" is lit, and the timer is running. The display
window will show the current humidity reading. The controller will send power
to its humidifying/dehumidifying outlets to regulate humidity. When the program
is running, press the PAUSE key to put the controller in Program Hold mode.
Program Hold: In this mode, the controller pauses the time but still regulates
the humidity at the current set value. Here, the "RUN" indicator is off. The
display window flashes between the measured humidity value and "Hold". To
resume the program, press the START key. To completely stop the program,
hold the STOP key for 4 seconds.
Program Stop: The current running program in the system is terminated.
Controller outputs are deactivated and timer is also stopped. The "RUN"
indicator is off. The display window flashes between the measured humidity
value and "Stop". To start the program, press the START key. The controller
will execute the program from the first step.
Programming Mode: This mode allows users to review/edit the humidity set
value and set time for each steps. When the controller is in Program Run, Hold,
or Stop mode, press the SET key to enter Programming mode. Please see
figure 4 for details.
2022.01
Controller
Power Up
Program
Program
START
Hold
Run
PAUSE
STOP
START
4 s
Program
Stop
Parameter Setting Mode: Review and edit system parameters. When the
controller is in Program Run, Hold, or Stop mode, hold the SET key for 2
seconds to enter the Parameter Setting mode. Please see figure 3 for details.
6. Parameter Setup
Please see Table 2 for a list of parameters and Figure 3 for the flow chart of how
to set the parameters. Please note that parameters will remain unchanged
unless you press set key to confirm the change.
Press and hold the SET key for 5s to enter the parameter settings. The top
display shows the parameter name, and the bottom display shows the current
value or option for this parameter. Use the up and down keys to adjust the value
or option in bottom display. Once finished, press SET key momentarily to confirm
and go to next parameter.
Table 2. List of Parameters.
Code
Description
AH
AH
Deviation high alarm
AL
AL
Deviation low alarm
Humidity Control
HY
HY
Hysteresis Band
Dehumidifier
HYd
Hyd
Hysteresis Band
Humidifier Hysteresis
HYH
HYH
Band
oFS
Ofs
Humidity Offset
Anti-short Cycle
AS
AS
Delay (only for
dehumidifying)
PrG
PrG
Program Modes
Power
A-M
A-M
Outage/Startup
Modes
Sensor Failure
SFA
SFA
Operation
TIM
time
Time unit
PSD
PSD
App access password
Note 1. AH, Deviation high alarm; AL, Deviation low alarm:
Assuming measured humidity is PV and set humidity is H. When PV - H is
above AH, the built-in buzzer will turn on (deviation high alarm); when H – PV
is above AL, the built-in buzzer will turn on (deviation low alarm). Users can
mute the alarm by momentarily pressing the Mute key. The alarm will remain
inactive until the process value moves out of the alarm zone. Both alarms are
deviation alarms, i.e., if AH = 20%, AL = 30%; and the Set Humidity (H) is 50%
RH, the alarm will be activated if the humidity is above 70% or below 20%. The
alarm function is suppressed at powering up or when the program jumps from
one step to another step. It will be activated automatically once the measured
humidity enters the none-alarm zone (between H - AL and H + AH).
Note 2. Hy, Humidity Control Hysteresis Band, or Humidity Control Dead Band:
This parameter sets up a hysteresis band (dead band) within which either the
humidifier or dehumidifier will not work (between H - Hy and H + Hy). The
minimum value for Hy is 0.5. The Hy value should not be too small if the
system has sluggish response. Otherwise, it may result in the humidifier and
the dehumidifier working against each other, wasting energy and causing
oscillation.
WWW.AUBERINS.COM
Setting
Initial
Note
Range
0 ~ 99.9
20.0
1
0 ~ 99.9
20.0
1
0 ~ 99.9
1.0
2
0 ~ 99.9
5.0
3
0 ~ 99.9
5.0
4
-9.9 ~ 9.9
0
5
M 0 ~ M 99
M 6
6
(0 ~ 99 min)
on, off
ON
7
S, M, C
S
8
0-0, 0-1, 1-0
0-0
9
H, M
H
10
000 - 999
666
11
P2/5