Auber Instruments AT210 Instruction Manual - Page 2
Browse online or download pdf Instruction Manual for Thermometer Auber Instruments AT210. Auber Instruments AT210 3 pages. Digital
Also for Auber Instruments AT210: Notes On Use (2 pages), Instruction Manual (3 pages), Instruction Manual (4 pages)
AUBER INSTRUMENTS
AH1 and AH2 are called alarm on temperature, i.e. the temperatures at which the
Alarm1 and Alarm2 will turn on; AL1 and AL2 are called alarm off temperature, i.e.
the temperatures at which the Alarm1 and Alarm2 will turn off. When AH1>AL1(or
AH2>AL2), the alarms is set as a high limit alarm. When AH1<AL1(or AH2<AL2), the
alarm is set as a low limit alarm. For a high limit alarm, the alarm buzzer should be
on once the temperature rise above AH, and it should be off only when the
temperature drops below AL. In contrast, for a low limit alarm, the alarm buzzer
should be on when the temperature drops below AH, and it should be off only when
the temperature rise above AL.
For example, when the temperature unit is set to F (Fahrenheit), AH1=900, and
AL1=800, the buzzer will go off once the measured temperature is higher than
900°F; the buzzer will stop when the temperature drops below 800°F. In another
case, when AH2=180, AL2=185, the alarm2 is set as a low limit alarm. If the
temperature drops below 180°F, the buzzer will go off (on); when the temperature
rises above 185°F, the buzzer will stop.
Users can press the Shift key (">") to mute the buzzer. The alarm will buzz again if
the alarm temperature moves out of the alarm zone (between AH and AL) and re-
enters it again. For instance, AH1=900, AL1=800, current temperature is higher than
900, and the alarm is muted. In this case, the temperature has to drop below 800
and rise above 900 again to trigger the alarm buzzer. To disable the alarms, set AH
and AL to the same value, i.e., AH1=AL1 and AH2=AL2.
Steps to set an alarm are described below as well as in the flow chart in Figure 4:
(1) Press SET key, change the code to 0001, and press SET again to enter alarm
setting mode.
(2) Press Up and Down key to select a parameter (AH1, AL1, AH2, or AL2).
(3) Press SET to view the value of the parameter.
(4) Use Shift, Up, and Down key to change the value.
(5) Press SET key to confirm the value and exit from this parameter.
(6) Press Up or Down key to select the new parameter.
(7) To exit this mode, press SET key when "End" is displayed.
The procedure is showed in the flow chart in Figure 4.
Parameter Display
Operation Mode
Enter Code
SET
SET
XXXX
0001
SET
Figure 4. Steps of setting alarms. In this example, alarm1 is set as a high limit alarm
at 480; alarm2 is disabled.
7. System settings (code 0089)
The parameters for system configuration is listed in Table 1.
Table 1. System configuration parameters.
Symbol
Name
Description
Inty
Input sensor type
Inty
PSb
PSb
Input offset
FILT
FILT
Digital filter
C-F
C-F
Temperature unit
Brit
Brit
Brightness level of dimmed LED
END
END
Note 1. Inty (Input sensor type). This parameter defines the sensor type that is used
for the thermometer. If you purchased the thermometer bundle, it is already set for
the probe included in the package. You don't need to change it.
Note 2. PSb (input offset). This is to set an offset value to compensate the error
produced by the sensor. For example, if the meter displays 5 ºC when probe is in ice/
water mixture, setting PSb= -5 will make the meter display 0 ºC.
Note 3. FILt (digital Filter). If the temperature reading fluctuates due to input noise, a
digital filter can be used to smooth the input signal. "FILt" may be configured in the
range of 0-3. Higher the value, stronger the filtering effect. A strong filter increases
the stability of the readout, but causes longer delay in responding to the temperature
change. Set FILt=0 will disable the filter.
Note 4. C-F (temperature unit). Set to C if you want to display temperature in
Celsius. Set to F for Fahrenheit.
2013.11
Buzzer On Temp
SET
SET
0480
AH1
Buzzer Off Temp
SET
SET
0479
AL1
Buzzer On Temp
SET
SET
0250
AH2
Buzzer Off Temp
SET
SET
0250
AL2
END
Setting Range
Initial
K
k
-1000 ~ 8000
0
0 ~ 3
0
°C, °F
°F
1-4
1
Exit
Note 5. Brit (display dimmer). This parameter sets the brightness level of the
dimmed LED display. You can switch the LED brightness level between the dimmed
and the normal using UP key. However, the normal brightness level of the LED
display is equal to level 4. So if Brit is set to 4, you won't see and change in the
brightness of LED display when pressing UP key.
Note 6. End. Exit the parameter setting mode.
Steps to set system parameters are described below as well as in the flow chart in
Figure 5:
(1) Press SET key, change code to 0089, and press SET again to enter the system
configuration mode.
(2) Press Up or Down key to select the parameter to be changed.
(3) Press SET to view the value of the parameter.
(4) Press Shift, Up, and Down key to enter a new value.
(5) Press SET to confirm.
(6) Press Up or Down to select the new parameter.
(7) To exit the menu, press SET when "End" is displayed.
Operation Mode
Enter Code
SET
XXXX
0089
SET
Figure 5. Flow chart of how to set system configuration parameters.
8. Wireless connection setting (code 0110)
The parameters for wireless connection can be accessed by code 0110. The
parameters are listed in Table 2.
Table 2. Wireless connection parameters.
Symbol
Name
bAud
bAud
Id
Id
Tdly
tdly *
Hand shake time
tACy
tACy *
Sampling rate
Note
End
End
1
2
Note 7. Baud (Baud rate for communication). This should be left as default.
Note 8. Id (Unit ID). Each slave unit should be assigned with a unique Unit ID. The
3
default value is 1. The value of the Unit ID can range from 0 to 240. A master unit can
4
communicate with up to 10 slave units. For example, if you have two slave units, you
5
can set their Unit ID to 1 and 2 respectively. Then, when the master Unit ID is set to 1, it
6
will read the temperature of slave unit 1. When the master Unit ID is set to 2, it will read
from slave unit 2. Set two slave units to the same ID number will cause crashes.
Note 9. tdly (Hand shake time). This is the time interval (unit in seconds) after which the
master unit will attempt to read signal from the slave unit again. If the master unit
receives signal during this hand shake time, it will refresh and display the current
reading at the assigned cycle rate. Otherwise, it will display the previous reading for the
rest of the current hand shake cycle. If there is still no signal received during the entire
hand shake time, the master unit will display four dashes ("- - - -"). This setting can
prevent the master unit from frequently switching between temperature reading and
four dashes. If the master unit and the slave unit is far away from each other or the
signal is weak, user should increase the hand shake time. Placing the master and slave
unit too close to each other may also result in no reading on the master unit.
Note 10. tACy (Sampling rate). This parameter sets how frequently the slave unit
refresh its reading . The default sampling rate is 1 per second. The unit is s
Note *. These two parameters are only available on the master unit.
WWW.AUBERINS.COM
Parameter Display
Input Type
SET
SET
xxxx
Inty
Input Offset
SET
xxxx
PSb
Digital Filter
SET
xxxx
FiLT
Temperature Unit
SET
xxxx
C-F
Brightness level of dimmed LED
SET
xxxx
Brit
End
Description
Setting Range
Baud rate
1200, 2400, 3600, 9600
Unit ID
0 ~ 240
2 ~ 60
0.5 ~ 60 per second
Exit
Initial
Note
9600
7
1
8
3.0
9 *
1.0
10 *
-1
or Hz.
P2/2