DuctSox SkeleCore Pull-Tight Cable Installation Manual - Page 4

Browse online or download pdf Installation Manual for Industrial Equipment DuctSox SkeleCore Pull-Tight Cable. DuctSox SkeleCore Pull-Tight Cable 16 pages.

SkeleCore Pull-Tight Cable

Installation Steps

1. Review materials in box, including the CAD drawing and installed location of the DuctSox
2. Prepare metal inlet collar for fabric connection
3. Mark placement and install cable. (3x1 or 4x2)
4. Install and assemble DuctSox components
5. Start up AHU
6. Balance airflow
Step 1
Review materials in box, including the project-specific drawing and installed location of the DuctSox. The Project-Specific
Drawings detail the specific locations of Tensioning Baskets and Cable Stops using the Inlet Belt as the main reference point.
READ INSTRUCTIONS THOROUGHLY BEFORE BEGINNING.
Example Project-Specific Drawing Detail
Step 2
Prepare metal inlet collar for fabric connection.
• Confirm inlet air supply location.
• Confirm inlet air supply size.
• DuctSox inlets are manufactured 1/2 in (12 mm) larger than specified
to fit over metal inlet collar.
• Metal collar length should be 6 in–10 in (150 cm to 250 cm) for
secure fabric attachment.
• Edge Guard (provided) should be installed on the edge of the metal
collar to reduce fabric wear from the metal edge.
4
Installation Manual
DuctSox
6 in–10 in
(150 cm–250 cm)
Edge Guard
(Supplied)
Publication: AMEN00417 2021-02-22
®