[Various settings]
■Item
Address number setting
■Common procedure for address writer operation
Be sure to connect to the AnyWireASLINK master unit to use.
An address writer ARW-04 (Ver.04-1.01 or higher) is required for
operation.
For details about the operation method, refer to the address
writer's Products Guide.
1. Connect the terminal to the master unit of the AnyWireASLINK system.
Set with the address writer while supplying the transmission signal (DP, DN).
Transmission
signal
* Make sure to use a 24V DC stabilized
power supply for the power supply to be
connected.
2. Setting is required for all terminals.
Direct the address writer toward the setting port (Fig. 1) of this product.
(Bring the emitter as close as possible to the setting port.)
Address number setting
The address number is used to set which number of the transmission
frame to start with for the terminal to occupy.
Set the address number in a range from "0" to "254."
The default address-number setting of the
CAUTION
terminal is "255," which means no setting.
If the address number setting is "255," the
terminal cannot perform input/output operations.
Make sure to use the terminal after setting the
address number within the range of "0 to 254."
Teaching

Parameter setting

Red: DP:
AnyWireASLINK
Master
Black: DN
24V DC*
Fig. 1
Setting port
-BSH03171K 6/8-
Teaching
Store the status when a work is present and when a work is absent in
the ASLINKSENSOR.
Carry out setting with the work actually used.
[SET ON setting]
Object to
be detected
[SET OFF setting]
No object to
be detected
[Teaching Automatic Setting]
In the SET ON/SET OFF setting, based on the difference of AD value
stored at the time of with or without a workpiece, "threshold,"
"hysteresis," "alarm value Hi," and "alarm value Lo" are automatically
set in the following %.
Parameter setting
■Setting of threshold
Set the threshold of the light receiving level to judge presence/absence
of detection.
* Difference in the detection state stored in teaching is 100%.
- Address writer (ARW-04): Parameter 01
AD value
0-100%
0 - 1023
0-100%
50 (AD value)
Default:
*The setting range depends on the setting of parameter 8.
■Setting of hysteresis
Set the change in the amount of the light receiving value required to
turn the detection state from ON to OFF.
- Address writer (ARW-04): Parameter 02
0-100%
AD value
0 - 1023
0-100%
Default:
*The setting range depends on the setting of parameter 8.
Red: DP
AnyWireASLINK
Master
Black: DN
Red: DP
AnyWireASLINK
Master
Black: DN
Threshold
50%
Hysteresis
5%
Alarm value Hi
80%
Alarm value Lo
20%
10 (AD value)