Danfoss ADAP-KOOL AK-PC 781 User Manual - Page 14
Browse online or download pdf User Manual for Controller Danfoss ADAP-KOOL AK-PC 781. Danfoss ADAP-KOOL AK-PC 781 14 pages. Capacity controller with heat recovery
Pc bar
Tc °C
Gc status
Pgc Bar
Pgc reference Bar
Sd discharge gas °C
Sgc °C
V1 Actual input
V2 Actual input
V3 Actual input
PI1 State
PI1 Alarm state
PI1 Input
PI1 Reference
PI1 Output value
PI1 Output type
Settings
Main switch
V1 Cutin
V1 Cutout
V1 Cutin delay m
V1 Cutout delay m
V1 High Al Limit
V1 Low Al Limit
V1 High Al delay m
V1 Low Al delay m
PI1 Off Aut Man
PI1 Manual OD
(Use Service Tool if data concerning Volt 2, 3, 4, 5 and PI2 /PI3 are to be downloaded).
AKM menu: "For DANFOSS only"
This menu contains data and setting values for special internal controller functions.
Do not change the stated values.
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
already on order provided that such alternations can be made without subsequential changes being necessary in specifications already agreed.
All trademarks in this material are property of the respecitve companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
14
Condensing pressure (measured with the pressure transmitter)
Condensing pressure in °C. (measured with the pressure transmitter)
Actual gas cooler operation:
0=Off. 1=Standby. 2=Max COP operation. 3=Heat recovery. 4=Extra capacity.
5=Manual control.
Actual gas cooler pressure
Actual reference for gas cooler pressure
Actual discharge gas temperature
Actual temperature at outlet from the gas cooler
Voltage measurement on the function defined in Volt 1.
Voltage measurement on the function defined in Volt 2.
Voltage measurement on the function defined in Volt 3.
PI function state
PI function alarm condition
Input signal
Reference
Output value
Output type: PWM. Stepper. Voltage
Main switch:
The value where the relay is to cut in
The value where the relay is to cut out
Time delay for cutin of relay
Time delay for cutout of relay
The value for the high alarm limit
The value for the low alarm limit
Time delay for high alarm
Time delay for low alarm
Control of PI function. 0: Off, 1: Automatic, 2: Manual
Manual setting of opening degree for PI function
Menu operation
RC8CE202 © Danfoss 03/2013
ON:
Regulation
OFF: Controller stopped
AK-PC 781 Version 4.1x