Danfoss AK-CC55 Installation Manual - Page 8

Browse online or download pdf Installation Manual for Controller Danfoss AK-CC55. Danfoss AK-CC55 18 pages. Single coil
Also for Danfoss AK-CC55: Installation Manual (16 pages)

Danfoss AK-CC55 Installation Manual
Operation with setting display
Display AK-UI55 Set
The values will be shown with three digits, and with a setting you can determine whether the temperature is to be shown in °C or in °F.
Lights up in event of:
Energy optimization
Cooling
Defrosting
Fan operation
The display can give the following messages:
-d-
Defrost is in progress
Err
The temperature cannot be displayed due to a sensor error
Err
The display cannot load data from the controller. Disconnect and then reconnect the display
ALA
The alarm button is activated. The first alarm code is then shown
- - -
Top position in the alarm queue
- - -
Bottom position in the alarm queue
Loc
The configuration is locked. Unlock by pressing (for 3 seconds) on the 'up arrow' and 'down arrow' simultaneously
UnL
The configuration is unlocked
- - -
The parameter has reached min. or max. limit
PS
A password is required for access to the menu
Fan
Appliance cleaning has been initiated. The fans are running
OFF
Appliance cleaning is activated and the appliance can now be cleaned
OFF
The main switch is set to Off
SEr
The main switch is set to service / manual operation
CO2
Flashes: Will display in event of a refrigerant leakage alarm, but only if the refrigerant is set up for CO2
Factory setting
If you need to return to the factory-set values, it can be done in this way:
- Cut off the supply voltage to the controller
- Keep up
arrow buttons depressed at the same time as you reconnect the supply voltage
"
" and down "
"
- When FAc is shown in the display, select "yes".
8 | AN294432763974en-000201
Lights in event of alarm — press on alarm button — alarm relay is reset — alarm code displayed — e.g. "A1"
Alarm codes are shown on page 17.
Long press (3 seconds) gives access to the
information menu "InF".
Up arrow / Down arrow / Arrow to left:
Navigation in the menu and setting of values.
Long press (3 seconds) will start a defrost, "dEF" is
shown in the display. Ongoing defrosting can be
stopped by a long press.
SET:
Long press (3 seconds) gives access to the "SEt" menu.
If the operation is locked with a password, "PS" is shown. Enter the code.
Shows the setting for a chosen parameter / saves a changed setting.
Short press gives access to entering of the thermostat's cut-out limit.