10. Technical data

Inputs
Outputs
Operating voltage (V)
Current consumption
Ambient temperature
Protection class
Protection class
Interference emission
Resistance to interference
Dimensions
Weight
12
DEN - SMT / PL
ThermoControl – 3
8 x Pt1000 two-wire sensors
1 x potential-free circuit for external disinfection
1 x potential-free circuit for temperature regulator (TR)
4 x potential-free circuits for pump fault inputs
1 x frequency input for flow sensor
3 x 3-point signal maximum load 230V AC, 2A
4 x pump power supplies, switched: maximum load 230V AC, 2A
4 x pump control signals PWM 5V level (100Hz)
4 x pump control signals 0-10V DC, input resistance > 100kΩ
including four switch outputs (on/off ) 5V level
1 x heat request, potential-free two-way contact, maximum load
230V AC, 2A
1 x fault message output, potential-free two-way contact, maximum load
230V AC, 2A
1 x 12V DC: maximum load 50mA
230V ±10%, 50-60Hz
max. 6.3A
0-40°C
IP 54
II as per VDE 0106
as per EN 61000-6-3
as per EN55011 + A1 : class B
as per EN 61000-6-2
(height x width x depth): 159 x 248 x 124 mm
1.6 kg
VM.GU.A1.02