Also for Danfoss iC7 Series: Installation Manual (8 pages), Installation Manual (6 pages), Installation Manual (14 pages), Installation Manual (16 pages), Installation Manual (8 pages), Installation Manual (8 pages), Installation Manual (10 pages), Installation Manual (16 pages), Installation Manual (16 pages), Installation Manual (6 pages), Installation Manual (6 pages), Installation Manual (16 pages), Installation Manual (18 pages)

Danfoss iC7 Series Installation Manual
IGBT Module Replacement for Fx09-Fx12 and E1h–E4h
Installation Guide
7.
Tighten the busbar connection terminals to the torque value listed in
Example
1
4
Illustration 3: IGBT Fastener Tightening Sequence
Table 7: Torque Tightening Values and Sequence for iC7 Series Frequency Converters
Kit number
Mounting torque
[Nm (in-lb)]
176F3944
3.3 (29)
176F3945
3.3 (29)
176F3949
3.3 (29)
176F3943
4.5 (40)
176F4141
3.3 (29)
176F4143
4.5 (40)
176F3950
3.3 (29)
176F3956
4.5 (40)
6 | Danfoss A/S © 2022.03
3
2
A
Busbar connection
torque [Nm (in-lb)]
3.3 (29)
3.3 (29)
3.3 (29)
9.0 (80)
3.3 (29)
9.0 (80)
3.3 (29)
9.0 (80)
Table 7
and
Table
8.
7
3
1
5
9
B
Diagram
A
A
A
B
A
B
A
B
AN361427984575en-000101 / 130R0770
Installation
10
6
2
4
8
Screw tightening order
1-2-3-4
1-2-3-4
1-2-3-4
1-2-3-4-5-6-7-8-9-10
1-2-3-4
1-2-3-4-5-6-7-8-9-10
1-2-3-4
1-2-3-4-5-6-7-8-9-10