Also for Danfoss iC7 Series: Installation Manual (8 pages), Installation Manual (8 pages), Installation Manual (6 pages), Installation Manual (14 pages), Installation Manual (16 pages), Installation Manual (8 pages), Installation Manual (8 pages), Installation Manual (10 pages), Installation Manual (16 pages), Installation Manual (6 pages), Installation Manual (6 pages), Installation Manual (16 pages), Installation Manual (18 pages)

Danfoss iC7 Series Installation Manual
In-back/Out-top Cooling Kit for FA09-FA10
Installation Guide
1
Mounting plate
2
M10x30 screw
3
Frequency converter
4
Mounting plate gasket (front)
5
Mounting holes
6
Cabinet back plate
2.7 Assembling the Top Duct
The top duct is a telescopic duct that collapse to simplify installation. To assemble the duct before installation, use the following
steps. Refer to
Illustration
10.
Procedure
1.
Cut the strip of ribbed EPDM rubber seal into 2 pieces. Use the following measurements:
a.
For FA09 frequency converters, cut 2 strips of 581 mm (22.9 in).
b.
For FA10 frequency converters, cut 2 strips of 849 mm (33.4 in).
2.
Peel the paper off the self-adhesive seals. Place 1 strip on the outside bottom edge of the inner sleeve of the duct, and 1
strip on the upper inside edge of the outer sleeve of the duct.
3.
With the rubber seal in place, carefully slide the inner sleeve of the duct into the outer sleeve.
1
2
3
Illustration 10: Assembly of Telescopic Ducts
12 | Danfoss A/S © 2022.03
7
Mounting plate gasket (back)
8
Back vent opening
9
M10 nut
10
Seal plate gasket
11
Seal plate
12
Notch in lower edge of frequency converter
AN371942666355en-000101 / 136R0250
Installation