8. Confirm the action of controller and positioner
– direct or reverse – are producing the de sired
response in the control unit. Con firm that the
control valve "fail" position is as re quired.
9. Hereafter, the procedure assumes that actual
fluid flow may be established. This may not
be practical/possible in all cases; if so, vary
pro ce dure as required.
Always "heat" or "cool" down the system pip ing
SLOWLY by opening the control valve station
bypass valve in small increments.
10. With one of the control valve station block
valves still closed, and the loop controller still
in "manual" mode, open bypass valve and vary
flow rate manually to observe the re sponse of
the controller and control valve unit together.
V. MAINTENANCE
WARNING
SYSTEM UNDER PRESSURE.
maintenance, isolate the valve/actuator from the sys tem
and relieve all pressure. Failure to do so could result in
personal injury.
A. General:
1. Maintenance procedures hereinafter are
based upon removal of the valve/actuator
unit from the pipeline where installed.
2. Owner should refer to Owner's procedures for
re mov al, handling and cleaning of non re us able
parts, i.e. gaskets, suitable sol vents, etc.
3. General service valves supplied from the
factory do not require use of any gasket
sealant.(See below for "oxygen cleaned"
valves.)
4. Valves originally supplied in accordance
with Option-55 require special cleaning
pro ce dures. Refer to Cashco Specification No.
S-1134 for details.
with Spec. #S-1134, the valve is suitable for
ox y gen service. Sealants and lubricants used
in reassembly of a valve unit for use in oxygen
service MUST be suitable for O
5. All indicated Item Numbers that are with
4
SECTION V
Prior to performing any
When in compliance
service.
2
11. Attempt to develop manual control of the
loop by opening/closing the manual bypass
as required, or by manually controlling
main stream flow as required.
12. When the control valve is partially open, crack
open slowly the closed block valve while
si mul ta neous ly closing the bypass valve.
Con tin ue this procedure until the bypass is
closed and the block valves are both fully
open. The system is still under "manual" mode
control, but all flow is passing thru the control
valve.
13. Vary controller "manual" SIG output until
match ing the "automatic" SIG output, then
change the mode of the controller over to
"automatic", and the loop will experience a
minimum of upset conditions, and will be in
automatic control.
re spect to the actuator assembly (AA) are in
parenthesis and underscored; i.e. (20). All
Item Numbers that are with respect to the body
assembly (BA) are not un der scored; i.e. (32).
Reference with respect to the positioner is in
double parentheses; i.e. ((AP)).
6. Special care must be exhibited when
ro tat ing the plug stem (4) in the body to
not mar that portion of the surface of the
stem (4) where it contacts with the packing
(10). To rotate the stem (4) use the jam nuts
or grasp stem with soft-jawed pliers. NOTE:
When using the jam nuts (17) to rotate the
stem (4), use the upper jam nut to rotate the
stem CW, and the lower jam nut to rotate
the stem CCW, when viewed from above the
valve stem.
7. Hereafter, whenever text has the following
notation, "(Note PA.)", the following text is
to be applied:
"For ATO-FC units ONLY, connect a
temporary air source to the actuator and
pressurize to a level sufficient to initiate
travel to approximately mid-stroke."
8. Hereafter, whenever text has the following
notation, "(Note RP.)", the following text is
to be applied:
IOM-987