Also for Danfoss VLT AutomationDrive FC 302: Operating Manual (16 pages), Installation Manual (20 pages), Installation Instructions (4 pages), Installation Instructions Manual (6 pages), Installation Instructions Manual (12 pages), Installation Manual (18 pages), Installation Instructions Manual (8 pages), Installation Instructions Manual (10 pages), Installation Manual (6 pages), Installation Manual (16 pages), Operating Instructions Manual (16 pages), Installation Instructions Manual (6 pages), Installation Manual (16 pages), Installation Manual (8 pages), Installation Instructions Manual (6 pages)

Danfoss VLT AutomationDrive FC 302 Installation Manual
IGBT Module Replacement for D1h–D8h Drives
Installation Guide
9.
Tighten the busbar connection terminals to the torque value listed in
1
4
Illustration 2: IGBT Fastener Tightening Sequence
Table 2: Torque Tightening Values and Sequence
Kit number
Mounting torque [Nm
(in-lb)]
176F3362
3.3 (29)
176F3363
3.3 (29)
176F3364
3.5 (31)
176F3365
3.5 (31)
176F3366
3.3 (29)
176F3367
3.5 (31)
176F3422
3.3 (29)
4 | Danfoss A/S © 2023.10
3
2
A
Busbar connection torque
[Nm (in-lb)]
4.0 (35)
4.0 (35)
9.0 (80)
9.0 (80)
4.0 (35)
9.0 (80)
4.0 (35)
Table
2.
7
3
1
5
9
B
Diagram
A
A
B
B
A
B
A
AN341428219214en-000201 / 130R0383
Installation
10
6
2
4
8
Screw tightening order
1-2-3-4
1-2-3-4
1-2-3-4-5-6-7-8-9-10
1-2-3-4-5-6-7-8-9-10
1-2-3-4
1-2-3-4-5-6-7-8-9-10
1-2-3-4