Danfoss VLT AutomationDrive FC 302 with Connectors Installation Instructions - Page 2
Browse online or download pdf Installation Instructions for DC Drives Danfoss VLT AutomationDrive FC 302 with Connectors. Danfoss VLT AutomationDrive FC 302 with Connectors 4 pages.
Installation Instructions
FC 302 with connectors - 4 motor connectors (134N3196)
Illustration 3.2 4 Motor Connectors
FC 302 with connectors - side view
Illustration 3.3 Side View
For overall dimensions, refer to the VLT
302 Design Guide.
NOTICE
®
See the VLT
AutomationDrive FC 302 Design Guide for
further information.
2
VLT® AutomationDrive FC 302 with Connectors
®
AutomationDrive FC
Danfoss A/S © Rev. 06/2014 All rights reserved.
4 Connectors
4.1 Overview
The frequency converter has 7 connectors plus 2 or 4 motor
connectors
Label
Connector
X1
Mains
X2.1-X2.4
Motor
X51
PROFIBUS - Male
PROFIBUS -
X52
Female
X11-X14
I/O box connector Phoenix I/O box
Table 4.1 Connectors
4.2 X1- Mains M23 (in M25) Male
General ratings
•
Pins 1, 2, 3 and 4: 480 V AC, maximum 15 A
•
Pins C and D: 30 V DC, maximum 3 A
•
Tightening torque: 1.5–2.0 Nm
Pin
Label
Connected to frequency
converter wiring schematic
1
L1
4
L2
3
L3
2
PE
D
0 V DC
C
24 V DC
Table 4.2 Wire/Connector Assignment for Plug X1
Mating part: Mains X1 (female)
Phoenix order number.: KK-0885/XX,XX
Description
Mains in M23 (in M25) Male
Motor connection M23 Female
PROFIBUS M12
PROFIBUS M12
Min. wire
[mm
91 (T1)
2.5
92 (T2)
2.5
93 (T3)
2.5
95 (PE)
2.5
35
2.75
36
2.75
MI04G102
2
]