Danfoss VLT FC 103 Installation Manual - Page 4

Browse online or download pdf Installation Manual for DC Drives Danfoss VLT FC 103. Danfoss VLT FC 103 6 pages. Igbt module replacement for d1h–d8h drives
Also for Danfoss VLT FC 103: Operating Manual (16 pages), Installation Manual (20 pages), Installation Instructions Manual (6 pages), Installation Manual (18 pages), Installation Instructions Manual (8 pages), Installation Instructions Manual (10 pages), Installation Manual (6 pages), Operating Instructions Manual (16 pages), Installation Manual (16 pages), Installation Manual (8 pages), Installation Instructions Manual (6 pages)

Danfoss VLT FC 103 Installation Manual
IGBT Module Replacement for D1h–D8h Drives
Installation Guide
9.
Tighten the busbar connection terminals to the torque value listed in
1
4
Illustration 2: IGBT Fastener Tightening Sequence
Table 2: Torque Tightening Values and Sequence
Kit number
Mounting torque [Nm
(in-lb)]
176F3362
3.3 (29)
176F3363
3.3 (29)
176F3364
3.5 (31)
176F3365
3.5 (31)
176F3366
3.3 (29)
176F3367
3.5 (31)
176F3422
3.3 (29)
4 | Danfoss A/S © 2023.10
3
2
A
Busbar connection torque
[Nm (in-lb)]
4.0 (35)
4.0 (35)
9.0 (80)
9.0 (80)
4.0 (35)
9.0 (80)
4.0 (35)
Table
2.
7
3
1
5
9
B
Diagram
A
A
B
B
A
B
A
AN341428219214en-000201 / 130R0383
Installation
10
6
2
4
8
Screw tightening order
1-2-3-4
1-2-3-4
1-2-3-4-5-6-7-8-9-10
1-2-3-4-5-6-7-8-9-10
1-2-3-4
1-2-3-4-5-6-7-8-9-10
1-2-3-4