Danfoss VLT FC Series Installation Instructions Manual - Page 5
Browse online or download pdf Installation Instructions Manual for DC Drives Danfoss VLT FC Series. Danfoss VLT FC Series 6 pages. Igbt module replacement for d1h–d8h drives
Also for Danfoss VLT FC Series: Installation Manual (12 pages), Installation Manual (8 pages), Installation Instructions Manual (6 pages), Instructions Manual (11 pages), Installation Manual (6 pages)
Installation Instructions
Drive Rating
[HP]
[kW]
208-230 V
30
22
JJN-125 125 A,
300 V, Class T
40
30
FWX-150A 150 A,
250 V
50
37
FWX-200A 200 A,
250 V
60
45
FWX-250A 250 A,
250 V
75
55
n/a
100
75
n/a
125
90
n/a
Table 1.12 Fuse Replacement
For hp/kW sizes not shown in this chart, see the supplied FC 102, FC 202, or FC 302 Operating Instructions.
VLT® FC Series Internal Fuse Replacement
FC 102/FC 202
460-480 V
575-600 V
JJS-60 60 A, 600 V,
JJS-50 50 A, 600 V,
Class T
Class T
JJS-80 80 A, 600 V,
JJS-60 60 A, 600 V,
Class T
Class T
JJS-100 100 A,
JJS-80 80 A, 600 V,
600 V, Class T
Class T
JJS-125 125 A,
JJS-100 100 A,
600 V, Class T
600 V, Class T
JJS-150 150 A,
JJS-125 125 A,
600 V, Class T
600 V, Class T
FWX-200A 200 A,
JJS-150 150 A,
500 V
600 V, Class T
FWX-250A 250 A,
JJS-175 175 A,
500 V
600 V, Class T
®
MI92D102 - VLT
is a registered Danfoss trademark
FC 302
208-230 V
460-480 V
FWX-150A 150 A,
JJS-80 80 A, 600 V,
250 V
Class T
FWX-200A 200 A,
JJS-100 100 A,
250 V
600 V, Class T
FWX-250A 250 A,
JJS-125 125 A,
250 V
600 V, Class T
n/a
JJS-150 150 A,
600 V, Class T
n/a
FWH-200B 200 A,
500 V
n/a
FWH-250A 250 A,
500 V
n/a
n/a
575-600 V
JJS-60 60 A, 600 V,
Class T
JJS-80 80 A, 600 V,
Class T
JJS-100 100 A,
600 V, Class T
JJS-125 125 A,
600 V, Class T
JJS-150 150 A,
600 V, Class T
JJS-175 175 A,
600 V, Class T
n/a