INSTALLATION OF BACK-CHANNEL COOLING KIT FOR FRAMES D3, D4 & E2
This instruction sheet is for the installation of back-channel cooling kits available for the VLT
series drives. These kits are designed and tested to be used with Rittal TS8 enclosures
1800, 2000 and 2200 mm in height. Other enclosure heights are not supported. In addition to
the enclosure a 200 mm vented base/plinth is required.
The minimum enclosure depth is 500 mm (600mm for E2 frame) and the minimum enclosure
width is 600 mm (800mm for E2 frame). The maximum depth and width are as required by
the installation. When using multiple drives in one enclosure mount each drive on its own
back panel and support along the mid-section of the panel. The ductwork kits are very similar
in construction for all frames. The D3 and D4 kits do not support "in frame" mounting of the
drives. The E2 kit is mounted "in frame" for additional support of the drive. These kits can be
used with IP00/ Chassis drives as listed in Table 1 and are suitable for use only with Rittal
TS8 IP20 and UL & NEMA 1 and IP54 and UL & NEMA 12 enclosures.
Using these kits as described removes 85% of the losses via the back channel using the
drive's main heat sink fan. The remaining 15% must be removed via the door of the Rittal
enclosure. (Refer to Note 2 on Page 2 for air flow requirements.)
Table 1. Applicable Frames
and Drives
All D3, D4 and E2 Frames
*** IP00 ONLY ***
VLT4000
(North America)
VLT5000
VLT5000FLUX
VLT6000
VLT8000
VLT HVAC
VLT Aqua
VLT Automation
Instruction No: 175R5640 V3
INSTRUCTIONS
Table 2. Kit Part Numbers
Rittal TS8
Frame D3
Enclosure
Kit Part No.
1800 mm
176F1824
2000 mm
176F1826
2200 mm
Aug 13, 2008 Page 1 VLT
Frame D4
Kit Part No.
176F1823
176F1825
NA
NA
®
is a registered trademark of Danfoss A/S
®
Frame E2
Kit Part No.
Does not
fit in 1800
mm
176F1850
176F0299