Danfoss DEVIreg 316 Installation Manual - Page 4

Browse online or download pdf Installation Manual for Thermostat Danfoss DEVIreg 316. Danfoss DEVIreg 316 12 pages. Self-limiting cables on drum
Also for Danfoss DEVIreg 316: Installation Manual (16 pages)

Danfoss DEVIreg 316 Installation Manual
Installation Guide
5

Thermostats/controllers

DEVIreg™ 330
DEVIreg™ 316
DEVIreg™ 610
DEVIreg™ 850 IV
DEVIreg™ Hotwater
DEVIreg™ Multi
The DEVIreg™ thermostat/controller must be commissioned as prescribed in the installation instruction and adjusted where
local conditions vary in relation to factory settings Before every heating season or at least once per year, check for faults in the
switchboard, thermostat and sensors
Each heating cable screen must be earthed in accordance with local electric regulations and connected to a residual current
device (RCD)
The DEVIreg™ thermostat must be commissioned as prescribed in the thermostat manual Recommended temperature setting is
according to Application Guide or Installation Guide
More information about thermostats and controllers can be found at www.devi.com.
Sensors:
• Sensors can be live (230 V) components and must be treated according to specific Installation Guide and local standards
• Sensors can be extended using cable with the same cable construction and cross sections (up to 50 m, sensors for DEVIreg™ 850 IV
should be extended according to Installation guide)
• See section 7 for specific installations
1 - Controller; 2 - DIN-rail; 3 - Electric cabinet; 4 - Cold lead connection; 5 - Sensor connection
4
Self-limiting cables on drum
Tank frost
Pipe tracing
protection
2
3
4
AN384935621519en-010101
Sprinkler
Domestic hot
systems
water
5
1
Roof and
gutter
DEVI