Danfoss DEVIreg 532 Installation Manual - Page 10

Browse online or download pdf Installation Manual for Thermostat Danfoss DEVIreg 532. Danfoss DEVIreg 532 16 pages. Electronic thermostat

3

Settings

How to change the minimum and maximum floor
temperatures
1.
Remove the adjustment button.
2.
Move the pins to the desired
positions.
3.
Put the adjustment button back
in place.
Note: Please be aware of the following:
The floor temperature is measured where the floor
sensor is placed.
The temperature of the bottom of a wooden floor can
be up to 10 degrees higher than the top.
Floor manufactures often specify the max
temperature on the top surface of the floor (usually
27-28 ˚C).
By default, the maximum floor temperature is set to
35 °C.
Always use a floor sensor or a room + floor sensor
combination to control floor heating. Without a floor
sensor, the temperature control may be less accurate
and you risk overheating the floor.
10
DEVIreg™ 532
3
2
40
30
50
20
Installation Guide
4
5
6