Manual control
Select control mode.
5 sec.
Go to manual mode.
Actuator M1 is opening (
)
Actuator M1 is closing (
)
Pump P1 is ON (
)
Pump P1 is OFF (
)
Select control mode.
Manual mode should only be used for maintenance purposes. In manual mode all control
and safety functions are deactivated!
30
VI.KT.F2.02
© Danfoss 06/2008
DH-SMT/DK
Placing the temperature sensors
It is important that the sensors are mounted in the correct position in your system.
The temperature sensor mentioned below are sensors used for the ECL Comfort series
which not all will be needed for your application!
Outdoor temperature sensor (ESMT)
The outdoor sensor should be mounted on that side of the building where it is less
likely to be exposed to direct sunshine. It should not be placed close to doors, windows
or air outlets.
Flow temperature sensor (ESMU, ESM-11 or ESMC)
Place the sensor max. 15 cm from the mixing point. In systems with heat exchanger,
Danfoss recommends that the ESMU-type to be inserted into the exchanger flow outlet.
Make sure that the surface of the pipe is clean and even where the sensor is mounted.
Return temperature sensor (ESMU, ESM-11 or ESMC)
The return sensor should always be placed in / on a pipe with return water flow.
Room temperature sensor (ESM-10, ECA 60 / 62 room panel or ECA 61 / 63 remote
control)
Place the room sensor in the room where the temperature is to be controlled. Do not
place it on outer walls or close to radiators, windows or doors.
DHW temperature sensor (ESMU or ESMB-12)
Place the DHW temperature sensor according to the manufacturer's specification.
Boiler temperature sensor (ESMU, ESM-11 or ESMC)
Place the sensor according to the boiler manufacturer's specification.
Flow / air duct temperature sensor (ESM-11, ESMB-12, ESMC or ESMU types)
Place the sensor so that it measures a representative temperature.
Surface temperature sensor (ESMB-12)
Place the sensor in the surface of the floor.
Valid for ESM-11: Do not move the sensor after it has been fastened in order to avoid damage
to the sensor element.
VI.KT.F2.02
DH-SMT/DK
© Danfoss 06/2008
31