Also for Danfoss ECL Comfort 296: User Manual (12 pages), Installation Manual (20 pages), Operating Manual (8 pages), Operating Manual (16 pages), Operating Manual (10 pages), Installation Manual (16 pages), Installation Manual (16 pages), Installation Manual (16 pages), Installation Manual (20 pages), Installation Manual (12 pages), Installation Manual (16 pages), Operating Manual (8 pages)

Danfoss ECL Comfort 296 Service Manual
Service guide

8.3 "Modbus" to "mains" separation

The surge / lightning protected Modbus cables "must be separated from
mains / switched mains signal" even for a short run. Other signals in
ECL 296 / 310 (M Bus, sensor signals, RS485 signals), which are meant
for indoor wiring, "must be separated from mains / switched mains
signal" even for a short run. Modbus signals may be taken along with
MBus, sensor signal and other RS485 signals.
Recommended:
1) = surge protector
1. Even for a short distance well separated (≥ 7mm) from mains
signal.
2. Mains signal must be grouped separately and clear distance is
maintained throughout the cable routing (from surge protected
signal to ECL 296 / 310 wiring)