Danfoss ECL Comfort 310 Installation Manual - Page 6

Browse online or download pdf Installation Manual for Thermostat Danfoss ECL Comfort 310. Danfoss ECL Comfort 310 7 pages. A302
Also for Danfoss ECL Comfort 310: Installation Manual (8 pages), Mounting Manual (4 pages), User Manual (12 pages), User Manual (12 pages), Installation Manual (4 pages), Installation Manual (16 pages), Installation Manual (20 pages), Service Manual (16 pages), Operating Manual (8 pages), Operating Manual (16 pages), Operating Manual (10 pages), Installation Manual (20 pages), Installation Manual (16 pages), Installation Manual (16 pages), Installation Manual (16 pages), Installation Manual (16 pages), Installation Manual (20 pages), Installation Manual (16 pages), Installation Manual (16 pages), Installation Manual (20 pages), Installation Manual (12 pages), Mounting Manual (20 pages), Mounting Manual (20 pages), Mounting Manual (12 pages), Mounting Manual (16 pages), Operating Manual (8 pages)

Danfoss ECL Comfort 310 Installation Manual
Installation Guide
ECL Comfort 210 and 310, extended heat cut-out

2.3 Summer/winter filter constant

The filter constant of 250 is applicable for average buildings. A
filter constant of 1 is close switching according to actual outdoor
temperature meaning low filtering (very "light" building).
A filter constant of 300 is then to be chosen if a big filtering is
needed (very heavy building).
For heating circuits where the heat cut-out is demanded according
to the same outdoor temperature for the whole year, but different
filtering is wanted, different dates have to be set in the "Heat
cut-out" menu enabling a selection of a filter constant different
from the factory setting.
These different values have to be set in both the "Summer" and
"Winter" menu.
Danfoss District Energy
6
DEN-SMT/DK
VI.GU.U1.02