Danfoss ECtemp 530 Installation Manual - Page 7
Browse online or download pdf Installation Manual for Thermostat Danfoss ECtemp 530. Danfoss ECtemp 530 16 pages.
Also for Danfoss ECtemp 530: Installation Instructions Manual (16 pages)
Danfoss ECtemp 530
2
Mounting Instructions
• Place the floor sensor in a conduit in an appropriate
place where it is not exposed to sunlight or draft from
door openings.
• Equally distant and >2cm from two heating cables.
• The conduit should be flush with the floor surface -
countersink the conduit if necessary.
• Route the conduit to the connection box.
• The bending radius of the conduit must be min 50mm.
Installation Guide
Place the thermostat at a suitable height on
the wall (typically 80-170cm.).
In wet rooms, place the thermostat accord-
ing to local regulation on IP classes.
Note: A floor sensor enables a more accurate
temperature control and is recommended in
all floor heating applications and mandatory
under wooden floors to reduce the risk of
over-heating the floor.
7