3. Technical specifi cations:
Technical data
Operation voltage:
Power consumption:
Relays:
- Resistive load:
- Inductive load:
Sensing unit:
Sensing values:
- 0°C:
- 20°C:
- 50°C:
Hysteresis:
Temperature range:
- 130:
- 131:
- 132:
Ambient temperature:
Frost protection:
LED indicator:
- No light:
- Red light:
- Green light
IP class:
Dimensions:
10
230 VAC +10% / -20%, 50 Hz
Max. 5W
250V ~ 16A
1A (power factor 0.3)
NTC 15 kOhm at 25° C
42 kOhm
18 kOhm
6 kOhm
~ 0,2° C
(0) 5-45° C
(0) 5-35° C
(0) 5-35° C, for temperature limiter: 20-50° C
-10º to +50°C
5ºC
The system is off
The temperature set point is not reached.
The temperature set point is reached.
30
82 mm x 82 mm x 36 mm