Dungs LGW A2P Series Operation And Assembly Instructions

Browse online or download pdf Operation And Assembly Instructions for Switch Dungs LGW A2P Series. Dungs LGW A2P Series 8 pages. Air pressure switch, air pressure switch with test button
Also for Dungs LGW A2P Series: Operation And Assembly Instructions (8 pages), Instructions Manual (12 pages), Operation And Assembly Instructions (6 pages)

Dungs LGW A2P Series Operation And Assembly Instructions
D
F
Betriebs- und
Montageanleitung
Luftdruckwächter
LGW...A2
FIN
Luftdruckwächter mit Prüftaste
LGW...A2P
RoHS
[mbar]
EN 1854
30 – 150 mbar
2,5 – 50 mbar
1 – 10 mbar
0,4 –
3 mbar
[ V ]
Ag
[A]
EN 1854
Einbaulage / Installation position / Position de montage / Posizione di montaggio
α
α
α
α
α
α
α
α
1 ... 8
GB
F
NL
E
Operation and assembly
instructions
Air pressure switch
LGW...A2
DK
S
Air pressure switch with test button
LGW...A2P
LGW...A2
Konform mit 2002/95/EG
Conform to 2002/95/EC
Conforme à la directive 2002/95/CE
Conforme alla direttiva 2002/95/CE
Max. Betriebsdruck /
Max. operating pressure/
Pression de service maxi.
Max. pressione di esercizio
p
= 500 mbar (50 kPa)
max.
Druckwächter/ Pressure Switch/
Pressostat/ Pressostato
Typ/Type/Type/Tipo
LGW...A2
LGW...A2P
nach / acc. / selon / a norme
DIN EN 1854
Einstellbereiche
Setting ranges
Plages de réglage
Campi di taratura
Ag-Kontakt/Ag-Contact
Contact Ag/Contatti Ag
~(AC) eff., min./mini 24 V
~(AC) max. /maxi. 250 V
=(DC) min./mini. 24 V
=(DC) max. /maxi. 48 V
Au-Kontakt/Au-Contact
ContactAu/Contatti Au
=(DC) min./mini 5 V
=(DC) max./maxi 24 V
Nennstrom/nominal current/courant nomi-
nal/corrente nominale ~(AC) 10 A
Schaltstrom/current on contact/courant de
commutation/corrente di intervento
~(AC) eff., min./mini 20 mA,
~(AC) max./maxi. 6 A cos ϕ 1
~(AC) max./maxi. 3 A cos ϕ 0,6
=(DC) min./mini. 20 mA
=(DC) max./maxi. 1 A
Standardeinbaulage
Standard installation position
Position de montage standard
Posizione standard
Bei waagerechtem Einbau schaltet der Druckwächter bei einem um ca. 0,5 mbar höheren Druck.
In the horizontal installation position the switching pressure is increased by approx. 0.5 mbar.
Monté horizontalement, le pressostat commute à une pression d´environ 0,5 mbar plus élevée.
Con montaggio orizzontale il pressostato scatta ad una pressione superiore di circa 0,5 mbar.
Bei Einbau waagerecht über Kopf schaltet der Druckwächter bei einem um ca. 0,5 mbar niedrigeren Druck.
When the pressure switch is mounted horizontally overhead, its switching pressure decreases by approx. 0.5 mbar.
Monté horizontalement à l´envers, le pressostat commute à une pression d´environ 0,5 mbar moins élevée.
Con montaggio orizzontale capovolto il pressostato scatta ad una pressione infeziore di circa 0,5 mbar.
Bei Einbau in einer Zwischeneinbaulage schaltet der Druckwächter bei einem vom eingestellten Sollwert maximal ± 0,5 mbar
abweichenden Druck.
When the pressure switch is mounted in an intermediate position, its switching pressure deviates by max. ± 0.5 mbar from the
setpoint.
Monté dans une position intermédiaire, le pressostat commute à une pression d´un maximum de +/- 0,5 mbar par rapport à la
valeur de consigne réglée.
Con il montaggio in una posizione intermedia il pressostato scatta ad una pressione diversa da quella nominale di max.
± 0,5 mbar.
I
P
Notice d'emploi et de
montage
Pressostat
LGW...A2
N
Pressostat avec touche de contrôle
LGW...A2P
°C
+70
0
-15
°C
+70
0
-15
°C
+85
0
-30
IEC 529
IEC 529
Au
[A]
EN 1854
Istruzioni di esercizio e
di montaggio
Pressostati per aria
LGW...A2
Pressostati per aria con tasto di prova
LGW...A2P
Umgebungstemperatur
Ambient temperature
Température ambiante
Temperatura ambiente
–15 °C ... +70 °C
Mediumstemperatur
Medium temperature
Température du fluide
Temperatura fluido
–15 °C ... +70 °C
Lagertemperatur
Storage temperature
Température de stockage
Temperatura stoccaggio
–30 °C ... +85 °C
Luft- und Rauchgase
Air and flue gases
Air, fumée et gaz brûlés
Gas di combustione e aria
Schutzart / Degree of protection
Protection / Protezione
IP 54 nach / acc. / selon / a norme
IEC 529 (EN 60529)
Nennstrom/nominal current/cou-
rant nominal/corrente nominale
=(DC) 20 mA
Schaltstrom/current on contact/cou-
rant de commutation/corrente di
intervento
=(DC) min./mini. 5 mA
=(DC) max./maxi. 20 mA