Also for Danfoss ECL Comfort 210: User Manual (12 pages), User Manual (12 pages), User Manual (6 pages), Installation Manual (4 pages), Installation Manual (20 pages), Operating Manual (10 pages), Installation Manual (7 pages), Installation Manual (16 pages), Installation Manual (16 pages), Installation Manual (16 pages), Installation Manual (16 pages), Installation Manual (20 pages), Installation Manual (16 pages), Mounting Manual (16 pages)

Danfoss ECL Comfort 210 Operating Manual
ECL Comfort 210 / 296 / 310, Floor (Screed) Drying Program
X5 (Start time for period 5)
X6 (Start time for period 6)
X7 (Start time for period 7)
X8 (Start time for period 8)
The time that must elapse from time X4 for controlling the set flow
temperature in the curing heating period.
Values: Set the times
If the temperature values, set at X4 and X5, are different, the
desired flow temperature changes gradually from the X4 value
to the X5 value.
12 | © Danfoss | 2017.08
10934
10935
10936
When X5 is set to a time value, the desired flow temperature starts
10937
with the value, set at X4.
If the curing heating period should not be used, X8 can be set 0 h
(zero hours).