Danfoss ECL Comfort 310 Service Manual - Page 9

Browse online or download pdf Service Manual for Control Unit Danfoss ECL Comfort 310. Danfoss ECL Comfort 310 16 pages. A302
Also for Danfoss ECL Comfort 310: Installation Manual (8 pages), Mounting Manual (4 pages), User Manual (12 pages), User Manual (12 pages), Installation Manual (4 pages), Installation Manual (16 pages), Installation Manual (20 pages), Operating Manual (8 pages), Operating Manual (16 pages), Operating Manual (10 pages), Installation Manual (20 pages), Installation Manual (7 pages), Installation Manual (16 pages), Installation Manual (16 pages), Installation Manual (16 pages), Installation Manual (16 pages), Installation Manual (20 pages), Installation Manual (16 pages), Installation Manual (16 pages), Installation Manual (20 pages), Installation Manual (12 pages), Mounting Manual (20 pages), Mounting Manual (20 pages), Mounting Manual (12 pages), Mounting Manual (16 pages), Operating Manual (8 pages)

Danfoss ECL Comfort 310 Service Manual
Service guide

7.3 Individual houses (without repeater)

1) = surge protector
As there is no repeater used in this node, there is no isolated channels created. S.Gnd is not connected to earth (PE).
Input cable (coming from central heating station) shield MUST be floating and output cable shield is connected to earth. Or the input and
output shield continuity is maintained and it is not connected to earth (As shown above).
This is to maintain single point earthing in each network, on common reference signal (S.Gnd) and shield cable (Refer section 5 point 5,
6).
VI.LV.H1.02
ECL 296 / ECL 310 Modbus
© Danfoss | 2017.06 | 9