Danfoss ECL Comfort 310 Operating Manual - Page 6

Browse online or download pdf Operating Manual for Control Unit Danfoss ECL Comfort 310. Danfoss ECL Comfort 310 16 pages. A302
Also for Danfoss ECL Comfort 310: Installation Manual (8 pages), Mounting Manual (4 pages), User Manual (12 pages), User Manual (12 pages), Installation Manual (4 pages), Installation Manual (16 pages), Installation Manual (20 pages), Service Manual (16 pages), Operating Manual (8 pages), Operating Manual (10 pages), Installation Manual (20 pages), Installation Manual (7 pages), Installation Manual (16 pages), Installation Manual (16 pages), Installation Manual (16 pages), Installation Manual (16 pages), Installation Manual (20 pages), Installation Manual (16 pages), Installation Manual (16 pages), Installation Manual (20 pages), Installation Manual (12 pages), Mounting Manual (20 pages), Mounting Manual (20 pages), Mounting Manual (12 pages), Mounting Manual (16 pages), Operating Manual (8 pages)

Danfoss ECL Comfort 310 Operating Manual
ECL Comfort 210 / 296 / 310, Floor (Screed) Drying Program
When the floor drying process is finished, a data log can be read
from the ECL Comfort controller by means of the "ECL Tool". The
data log can be used for documenting the process.
The favorite display with temperature information of the heating
circuit(s) can, as an example, look like this:
Floor drying process not active:
Floor drying process active:
The progress bar is filled up from left side, according to time
elapsed since process start. The elapsed time and total process
time is also indicated in hours.
Return temperature related indications are not present, as the
return temperature limitation is cancelled during the floor drying
process.
Floor drying process being active can also be seen:
Circuit x > MENU > Influence overview > Des. flow T:
Before start of the floor drying process:
The control parameters must be set correctly (Circuit x > MENU
> Settings > Control parameters). See the Operating Guide for
the application in question.
The Time & Date must be set correctly (Common controller
> MENU > Time & Date). See the Operating Guide for the
application in question. The Time & Date settings are used in
the log facilities.
6 | © Danfoss | 2017.08
The mode selector of the ECL Comfort controller must not be in
Manual mode when the floor drying process is in progress.
VI.JM.P2.02