Dungs MPA 4112 V2.0 User Manual - Page 11
Browse online or download pdf User Manual for Burner Dungs MPA 4112 V2.0. Dungs MPA 4112 V2.0 16 pages. Automatic burner control system
Also for Dungs MPA 4112 V2.0: User Manual (16 pages)
15. Flame sensor: ionisation electrode
Single electrode operation, ionisation
MPA connector
15: Ignition
3: N
4: PE
5: ION*
7: FLW power
16: FLW2 NO
*When using a DUNGS DEZ 1xx SEO ignition transformer for single electrode operation,
the green / yellow line must be connected to terminal 5.
Two electrode operation, ionisation
MPA connector
15: Ignition
3: N
4: PE
5: ION
7: FLW power
16: FLW2 NO
11 ... 16
16. Approved flame detectors
Manufac-
turer
Flame
DUNGS
DUNGS
DUNGS
BST
Solutions
BST
Solutions
Flame
Designation
Type
Output
signal
Ionisation
Ionisation
Ionisation
–
electrode
UV tube
Ionisation
UV41 (HE)
UV tube
Switching
UV42
output
230 VAC
Ionisation
Switching
FLW 41I
output
230 VAC
FLW 20
(KLC 1000)
KLC 10/230
KLC 1000/230
FLW 20 UV
UV tube
Ionisation
KLC 10/230 RA
KLC 1000/230
RA
FLW 10 IR V2.1
KLC 2002
Flicker
FLW 10 IR
detection
with
KLC 2002
Ionisation
frequency
FLW 10 IR V2.1
monitoring
KLC 20/230
When using flame detectors, the reation times must be observed and adjusted by correctly setting the
corresponding parameters.
Safety
Total reacti-
Inter-
Continuous
time
on time after
mit-
operation
Flame
flame lift-off
tent
detector
0 s
P41
Yes
No
0,125 s
P41 + 0,125 s
Yes
No
(= 2/16 s)
0,125 s
P44 + 0,125 s
Yes
No
(= 2/16 s)
0,19 s
P44 + 0,19 s
Yes
No
(= 3/16 s)
0,5 s
P41 + 0,5 s
Yes
No
0,5 s
P41 + 0,5 s
Yes
No