Danfoss VLT HVAC Drive FC 102 Installation Instructions Manual - Page 7

Browse online or download pdf Installation Instructions Manual for Control Unit Danfoss VLT HVAC Drive FC 102. Danfoss VLT HVAC Drive FC 102 8 pages. Adjustable frequency drive - safe torque off
Also for Danfoss VLT HVAC Drive FC 102: Operating Manual (16 pages), Installation Manual (20 pages), Installation Instructions Manual (6 pages), Installation Instructions Manual (12 pages), Installation Manual (18 pages), Installation Instructions Manual (11 pages), Installation Instructions Manual (10 pages), Installation Manual (6 pages), Operating Instructions Manual (16 pages), Installation Instructions Manual (6 pages), Installation Manual (16 pages), Installation Manual (8 pages), Instruction Manual (16 pages), Installation Instructions Manual (6 pages), Installation Manual (6 pages)

Danfoss VLT HVAC Drive FC 102 Installation Instructions Manual
Installation Instructions
1.5 Mains Fuse Replacement Table
Single-phase drives
To replace the same type of mains fuse installed in the unit, refer to Table 1.14. For a list of maximum mains fuse sizes that can be
installed in the unit, or for hp/kW sizes not shown in this chart, refer to the operating guide.
Unit rating
[kW]
[hp]
208–230 V
0.37
0.5
0.55
0.75
0.75
1
1.1
1.5
LP-CC-15 15 A, 600 V, Class CC
1.5
2
JJN-20 20 A, 300 V, Class T
2.2
3
JJN-30 30 A, 300 V, Class T
3
4
JJN-35 35 A, 300 V, Class T
3.7/4
5
JJN-50 50 A, 300 V, Class T
5.5
7.5
JJN-60 60 A, 300 V, Class T
7.5
10
JJN-80 80 A, 300 V, Class T
11
15
15
20
FWX-150 150 A, 250 V
18.5
25
22
30
FWX-200 200 A, 250 V
30
40
37
50
45
60
55
75
75
100
90
125
Table 1.14 Mains Fuse Replacement (Single-phase)
MI92D402
Internal Mains Fuse Replacement for VLT
FC 102/FC 103/FC 202/FC 301/FC 302
FC 102/FC 103/FC 202
460–480 V
Danfoss A/S © 10/2018 All rights reserved.
®
Drives, 0.25–90 kW (0.3–125 hp)
575–600 V
208–230 V
FC 301/FC 302
460–480 V
575–600 V
7