Danfoss 180U3301 Installation And Commissioning Instructions - Page 6

Browse online or download pdf Installation And Commissioning Instructions for Water Pump Danfoss 180U3301. Danfoss 180U3301 12 pages.

9. Water connection:

Water supply
Checking the water supply pressure
High-pressure connection
6
Water supply
Connection of water supply, filter, low-pressure switch and manometer
are integrated in the common connection block of the Plug&Spray
unit.
The Plug&Spray
such as water from a reverse osmosis plant.
Included in the consignment are a ball valve, rotating fittings and a
check valve preventing return flow into the supply.
The water temperature must be kept between +3 and +50°C, respec-
tively 37 and 122°F.
The supply pressure must not exceed 2 and 4 bar. In case of unstable or
peak water pressure, a pressure reduction valve and an electrical shut
off valve are recommendable.
A supply pressure of at least 2 bar/29 psi is recommended to compen-
sate for the pressure loss in the filter element depending on the degree
of contamination. The low-pressure protection switch is set to 1,6 bar.
Make sure that the water supply pressure is neither insufficient nor
excessive. Check the reading of the manometer.
The manometer measures the pressure after the filter and can thus be
used to monitor the filter condition.
Cavitation or over-pressurization can cause severe damage to the
pump.
Two high-pressure connections are integrated in the common
Plug&Spray
The ports are G 3/8" female. One of the connections is plugged from
factory.
On request, a 3/8" NPT adapter is available.
521B0881 DKCFN.PI.020.F1.02
units can operate on tap water or technical water,
TM
connecting block.
TM
TM