NX Burner With Blocked Vent Safety (BVS) Operation
External Action
Power applied to burner control
Thermostat Calls For Heat
Call for heat is satisfied.
Reset button pushed two times
without device completing a call for
heat.
GeniSys 7505 Reset Button Operations
Pushing the reset button in the current state will cause the following conditions:
If the burner state is:
Lockout
Valve On Delay, Trial For
Ignition, Ignition Carryover
Run (igniter is shut off)
Motor-Off Delay, Standby
Pump Prime
Status Lights
Light Color
Red
Green
Yellow
OPERATION AND TROUBLESHOOTING
Appliance Response
Internal safety check conducted. If no light or flame is detected and all internal conditions are correct,
control enters idle mode.
1. Contacts between T and T on Aquastat L7248A are closed.
2. Burner Control period (4 seconds) internal and external check for flame or light. If flame is detected, control remains in
idle mode.
3. When flame is not present, Burner Control will apply power to the burner motor and igniter, complete a 15 second
valve on delay period and then apply power to the oil valve circuit.
4. Burner Control enters the trial for ignition period.
A. Monitors burner for flame.
B. When flame is not detected:
I. Enters lockout mode after 15 seconds.
II. Shuts off valve, igniter and burner motor.
III. Flashes indicator light at 1 Hz (½ second on, ½ second off).
IV. Depress reset button to return to power up sequence.
C. When flame is detected, Carry-Over period begins:
5. Burner Control enters 10-second Ignition Carry-Over period.
A. Turns on indicator light
B. If flame is lost and lockout time has not expired, Burner Control returns to trial for Ignition period.
C. If flame is lost and lockout time has expired, Burner Control enters Recycle Mode.
6. Carry-over time expires and igniter turns off.
7. Enters a run mode:
A. Flame is monitored until call for heat ends or flame is lost. If flame is lost:
B. Control enters Recycle Mode.
I. Recycle time starts (60 seconds).
II. Burner and valve are turned off.
III. Indicator light flashes at ¼ Hz (2 seconds on, 2 seconds off).
IV. Returns to Idle mode at end of Recycle mode.
1. Oil valve circuit is de-energized and valve shuts off.
2. Burner motor runs for selected post purge time.
3. Burner motor turns off.
4. Burner Control returns to Idle mode
1. Burner Control enters restricted mode.
2. Indicator light flashes 1 Hz (½ second on, ½ second off).
3. Reset device by pressing and holding reset button for a minimum of 45 seconds.
Pushing the reset button < 1 second
Reset from Soft Lockout
Pump Prime
Yellow light flashes to indicate cad cell
resistance.
No action
No action
On Continuously
Restricted (Hard) Lockout
Flame Sense during normal operation.
May be stray light during standby.
Control is in Pump Prime mode OR
reset button is currently held for >15
seconds.
Pushing the reset button > 1 second
Disable the Burner. Any time the
burner is running, press and hold the
reset button to disable the burner. The
burner will remain off as long as the
button is held.
Exit pump prime mode and return to standby.
Flashing
Soft Lockout
Recycle
Cad cell resistance.
14
Push, hold reset button >15
seconds
Reset from Restricted (Hard)
Lockout
Enables pump priming: After the
reset button has been held for 15
seconds the button can then be
clicked during the next ignition
sequence to enter pump prime
mode.
P/N 240009355, Rev. C [11/15/2015]