Danfoss RSH 95/125 Installation Manual - Page 2

Browse online or download pdf Installation Manual for Water Pump Danfoss RSH 95/125. Danfoss RSH 95/125 4 pages.

Danfoss RSH 95/125 Installation Manual
Installation Guide
DK
Oliepumpe type RSH
Tekniske data
Olietyper
Viskositetsområde:
- selvansugende
- med fødetryk
Omdrejningstal
Trykområde:
- med specialfjeder
Fabriksindstilling
Medietemperatur
Max. føde- og returtryk
Tilslutninger (fig. 1)
P = dysetilslutning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G 1/ 4
S = sugeledning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G 1/ 4
Fødetryksmåling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G 1/ 4
R = returledning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G 1/ 4
M = trykmåling/udluftning . . . . . . . . . . . . . . . . . . . . . . . . G 1/8
Bemærk!
Samtlige tilslutninger har anslået pakflade beregnet for
standardfladepakninger.
Type RSH leveres som 1-strengs pumpe med omløbet
"G" åbent (fig. 4).
Ved 2-strengs drift monteres den medleverede skrue "A"
i omløbet "G" (fig. 5).
Pumperne er selvansugende ved viskositeter op til
20 mm
/s. Ved højere visikositeter bør pumpen forsynes
2
med positivt fødetryk.
Ved 1-strengs drift med underliggende tank bør dyse-
ledningen monteres i udluftningsporten "M" og dyse-
porten "P" afblændes. Der skal her anvendes en afskæ-
rings-/lukkeventil på dyseledningen.
Omdrejningsretning
Set fra akselenden har en højregående pumpe omdrej-
ningsretning med uret, og en venstregående mod uret.
Udluftning
Ved 1-strengs anlæg udluftes pumpen ved 1-gangs
opstart via udluftningsstudsen "M" (fig. 2).
Ved 2-strengs anlæg udlufter pumpen automatisk
gennem returledningen.
Trykindstilling
Fig. 3 viser trykindstilling af en RSH pumpe. Maks. tryk
er afhængig af trykområde.
1-gangs opstart
Med let fyringsgasolie startes brænderen og pumpen
justeres til det ønskede tryk.
Med svær fyringsolie justeres til min. tryk. Pumpen drejes
langsomt til der er varm olie fremme ved trykmålestudsen.
Brænderen startes og pumpen justeres jævnt op til det
ønskede drifttryk.
Samme metode anvendes efter driftstop hvor olien er
blevet helt eller delvis kold.
Efter denne indjustering arbejder pumpen under normale
driftsbetingelser.
Anlæg
Installationen skal forsynes med forfilter efter gældende
regler/praksis.
Medier
Pumpen er specificeret for drift med mineralske brænd-
selsolier, henholdsvis medier med tilsvarende eller hø-
jere klassifikation.
Tilbehør
Til RSH-serien kan der leveres en løs flange incl. 4 skruer
til montage på halsens anlægsflade.
Bestillingsnummer: 070-0211
2
07/2012
RSH
Oil pump type RSH
Technical data
Standard fyringsolie
Oil types
og bio olie (FAME)
Viscosity range:
4,3 - 20 mm
/(cSt)
- self-priming
2
20 - 760 mm
/(cSt)
- with feed pressure
2
1400 - 3450 min
Speed
-1
15 - 35 bar (x 10
kPa)
Pressure range:
2
1 - 5 bar (x 10
kPa)
- with special spring
2
21 bar (x 10
kPa)
Default settings
2
-10 til +120 °C
Temperature of medium
4 bar (x 10
2
kPa)
Max. feed and return pressure
Connections (fig. 1)
P = nozzle connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . G 1/ 4
S = suction connection . . . . . . . . . . . . . . . . . . . . . . . . . . . G 1/ 4
Feed pressure measurement . . . . . . . . . . . . . . . . . . . . . . G 1/ 4
R = return line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G 1/ 4
M = pressure measurement/bleed . . . . . . . . . . . . . . . . . G 1/8
Note!
All connection surfaces are spotfaced for standard
gaskets.
RSH is supplied as a 1-pipe pump with bypass "G" open
(fig. 4).
For 2-pipe operation, screw "A" supplied must be fitted
in bypass "G" (fig. 5).
The pumps are self-priming for viscosities up to 20 mm
For higher viscosities, the pump should be connected
to positive feed pressure.
For 1-pipe operation with underlying tank, the nozzle
line should be connected to vent port "M", with nozzle
port "P" blanked off. In this case a shut-off valve must be
installed in the nozzle line.
Direction of rotation
The direction of rotation of a righthand pump is clock-
wise, a lefthand pump counterclockwise, when looking
on the end of the shaft.
Venting
On 1-pipe operation the pump is vented on first-time
starting via vent port "M" (fig. 2).
On 2-pipe operation the pump is vented automatically
through the return line.
Pressure settings
Fig. 3 shows the pressure setting of an RSH pump. Max.
pressure is dependent on the pressure range.
First-time starting
With light fuel oil, the burner must be started and the
pump adjusted to the required pressure.
With heavy fuel oil the setting must be on minimum
and the pump turned slowly, until hot oil appears at the
pressure measurement connection.
The burner can then be started and the pump adjusted
evenly up to the required operating pressure.
The same method must be used after an operational stop
when the oil has become partially or completely cold.
After this adjustment has been made the pump will run
under normal operating conditions.
Installation
A prefilter must be installed, in accordance with current
rules/practice.
Media
The pump is specified for operation with mineral-based
fuel oils, or media having a corresponding or higher
classification.
GB
Standard fuel gas oil
and bio oil (FAME)
4,3 - 20 mm
/(cSt)
2
20 - 760 mm
/(cSt)
2
1400 - 3450 min
-1
15 - 35 bar (x 10
kPa)
2
1 - 5 bar (x 10
kPa)
2
21 bar (x 10
kPa)
2
-10 to +120 °C
4 bar (x 10
2
kPa)
/s.
2
BIDFS352
Accessories
A separate flange with four screws for mounting on the
neck of the pump can be supplied for the RSH series.
Code no. 070-0211
The RSH can be used as a feed/transport pump after the
pressure setting spring has been replaced.
A replacement pressure setting spring with a range of
1-5 bar (x 102 kPa) together with a label giving the cor-
rect pressure range are obtainable under code number
070-0030.
DE
Ölpumpe Typ RSH
Technische Daten
Öltypen
und Bio Öl (FAME)
Viskositätsbereich:
- selbstansaugend
4,3 - 20 mm
- mit Speisedruck
20 - 760 mm
Drehzahl
Druckbereich:
15 - 35 bar (x 10
- mit Spezialfeder
1 - 5 bar (x 10
Werkseinstellung
Medientemperatur
Max. Speise- und
Rücklaufdruck
Anschluß (Fig. 1)
P = Düsenanschluß . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G 1/ 4
S = Saugleitung . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G 1/ 4
Speisedruckmessung . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G 1/ 4
R = Rücklaufleitung. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G 1/ 4
M = Druckmessung/Entlüftung . . . . . . . . . . . . . . . . . . . . G 1/8
Achtung!
Sämtliche Anschlüsse haben Dichtflächen für Standard-
Flachdichtungen.
Typ RSH wird als 1-Strang-Pumpe mit offenem Umlauf
"G" geliefert (Fig. 4).
Bei 2-Strang-Betrieb ist die mitgelieferte Schraube "A" in
den Umlauf "G" zu montieren (Fig. 5).
Die Pumpen sind selbstansaugend bei Viskositäten bis
20 mm2/s. Bei höheren Viskositäten ist die Pumpe an
positiven Speisedruck anzuschließen.
Bei 1-Strang-Betrieb mit tieferliegendem Tank muß die
Düsenleitung in die Entlüftungsöffnung "M" montiert
und die Düsenöffnung "P" verschlossen werden. Hier
muß ein Abschneide-/Schließventil an der Düsenlei-
tung angewendet werden.
Drehrichtung
Auf das Wellenende gesehen, läuft eine rechtdrehende
Pumpe im Uhrzeigersinn und eine linksdrehende gegen
den Uhrzeigersinn.
Entlüftung
Bei 1-Strang-Anlagen ist die Pumpe bei der erstmaligen
Inbetriebnahme durch den Entlüftungsstutzen "M" zu
entlüften (Fig. 2).
Bei 2-Strang-Anlagen entlüftet die Pumpe automatisch
durch die Rücklaufleitung.
Druckeinstellung
Fig. 3 zeigt die Druckeinstellung einer RSH-Pumpe. Der
max. zulässige Druck ist vom Druckbereich abhängig.
Erstmalige Inbetriebnahme
Bei leichtem Heizöl Brenner einschalten und die Pumpe
auf den gewünschten Druck einjustieren.
Bei schwerem Heizöl auf min. Druck einjustieren. Pumpe
langsam drehen, bis warmes Öl am Manometeranschluß
austritt.
Brenner einschalten und den gewünschten Betriebs-
druck der Pumpe gleichmäßig einjustieren. Nach Be-
triebsunterbrechungen mit abgekühltem oder kaltem
Danfoss Heating Solutions
Standard Heizöl
/(cSt)
2
/(cSt)
2
1400 - 3450 min
-1
kPa)
2
kPa)
2
21 bar (x 10
kPa)
2
-10 bis +70 °C
4 bar (x 10
kPa)
2