Danfoss 176F4188 Installation Manual - Page 2
Browse online or download pdf Installation Manual for Media Converter Danfoss 176F4188. Danfoss 176F4188 6 pages. Ground bar kit for fk11/fb11 and fk12/fb12, frequency converters
Ground Bar Kit for FK11/FB11 and FK12/FB12
Installation Guide
2 Installation
2.1 Safety Information
QUALIFIED PERSONNEL
Only qualified, Danfoss authorized personnel are allowed to install the parts described in these installation instructions.
-
Disassembly and reassembly of the frequency converter must be done in accordance with the service guide.
-
Use the standard fastener torque values from the service guide, unless the torque value is specified in these instructions.
DISCHARGE TIME (40 MINUTES)
The frequency converter contains DC-link capacitors, which can remain charged even when the frequency converter is not pow-
ered. High voltage can be present even when the warning LED indicator lights are off. Failure to wait 40 minutes after power has
been removed before performing service or repair work can result in death or serious injury.
-
Stop the motor.
-
Disconnect AC mains and remote DC-link power supplies, including battery back-ups, UPS, and DC-link connections to other
frequency converters.
-
Disconnect or lock the motor.
-
Disconnect any brake option.
-
Disconnect any DC connector option.
-
Wait 40 minutes for the DC-link capacitors to discharge fully.
-
Before performing any service or repair work, measure the voltage level to verify that the capacitors are fully discharged.
ELECTRICAL SHOCK HAZARD
The frequency converter contains dangerous voltages when connected to mains voltage. Improper installation, and installing or
servicing with power connected, can cause death, serious injury, or equipment failure.
-
Only use qualified electricians for the installation.
-
Disconnect the frequency converter from all power sources before installation or service.
-
Treat the frequency converter as live whenever the mains voltage is connected.
-
Follow the guidelines in these instructions and local electrical safety codes.
ELECTROSTATIC DISCHARGE
Electrostatic discharge can damage components.
-
Ensure electrostatic discharge before touching internal frequency converter components, for example by touching a groun-
ded, conductive surface or by wearing a grounded armband.
2.2 Assembling the Ground Bars
The ground bar kit includes 2 ground bars, 1 for the mains input side and 1 for the motor side of the frequency converter. Use the
following steps to assemble the ground bars before installation.
st
1.
Place the 1
ground bar over the 2 threaded posts on 1 of the angle brackets.
2.
Fasten 2 M6 hex nuts (T30) to the bracket posts, 1 on each post.
Torque to 3.9 Nm (35 in-lb).
2 | Danfoss A/S © 2022.10
N O T I C E
W A R N I N G
W A R N I N G
N O T I C E
Installation
AN422349925420en-000101 / 136R0287