Danfoss VLT AutomationDrive FC 302 Installation Instructions Manual - Page 5

Browse online or download pdf Installation Instructions Manual for Media Converter Danfoss VLT AutomationDrive FC 302. Danfoss VLT AutomationDrive FC 302 6 pages. Igbt module replacement for d1h–d8h drives
Also for Danfoss VLT AutomationDrive FC 302: Operating Manual (16 pages), Installation Manual (20 pages), Installation Instructions (4 pages), Installation Instructions Manual (12 pages), Installation Manual (18 pages), Installation Instructions Manual (8 pages), Installation Instructions Manual (10 pages), Installation Manual (6 pages), Installation Manual (16 pages), Operating Instructions Manual (16 pages), Installation Instructions Manual (6 pages), Installation Manual (16 pages), Installation Manual (8 pages), Installation Instructions Manual (6 pages), Installation Manual (6 pages)

Danfoss VLT AutomationDrive FC 302 Installation Instructions Manual
Installation Instructions
3.
Remove all control cables from the metal bracket
(spring-loaded).
4.
Remove any A, B, or C options that may be installed.
5.
Remove the I/O terminals.
1
Location of A option
2
Location B option
3
I/O terminals
Illustration 1.5 Location of Options and I/O Terminals
MI93A102
®
Control Card VLT
FC Series
6.
7.
1
2
3
Illustration 1.6 Location of Cable Shield, Screws, and MCO Ribbon
Cable
Danfoss A/S © 03/2017 All rights reserved.
Unscrew the 3 T10 screws and remove the cable
shield.
Remove the plastic cover underneath the cable
shield.
Cable shield
MCO ribbon cable
T10 screws