Duomo BX116 Manual - Page 7

Browse online or download pdf Manual for Gas Detectors Duomo BX116. Duomo BX116 7 pages.

Duomo BX116 Manual
Commissioning
It is strongly recommended that this detector should be commissioned by Duomo Commissioning Engineers or
engineers approved by Duomo to carry out this work. A quotation for commissioning or service will be provided upon
request. Fax site details and preferred date for commissioning to 01905 774296 and the Duomo Service Department will
fax back confirmation.
The benefits of this equipment being commissioned by Duomo are:
On board spares. If for whatever reason this equipment doesn't function correctly Duomo engineers will have spares on
board to ensure that the commissioning is successful.
A Duomo Commissioning Certificate is provided.
It is prudent to make electrical connection to the detector terminal plus when withdrawn and leave the plug off the
detector so that the Duomo Engineer is the first to power up the unit on site. This allows wiring to be checked prior to
commissioning and avoids damage due to incorrect connection. Guarantees for this product will become void if damage
is caused by the installer.

Technical specification

Power Supply
Secondary Battery
Power Consumption
Power Consumption
Relay contact range
st
1
pre-alarm
Main alarm
Sensor fault
No. of remote sensors
MIcro switches to include/exclude sensors
Monitored gas indication
Input signal
Device precision
Reaction time
Microprocessor
Working temperature
Start-up self diagnostic delay
Suitable for use with sensor type
Maximum distance for sensor connection
Cable diameter for sensors
Dimemsions
Protective rating
Guarantee
Duomo gas proving systems - Duomo gas detection - Duomo carbon dioxide sensors - Duomo ventilation interlocks - Are available direct or from all major stockists - www.duomo.co.uk
230V AC 50Hz +/- 10%
12V DC +/- 10%
30W maximum @ 230V
25W maximum @ 12V
10A 230V resistive - 5A 30V DC resistive
Can be set from 8% L.E.L. (120
Fixed at 20% L.E.L. / 300
ppm
Short circuit, interruption, sensor deterioration
16
1 per sensor
Through illuminated display
4 - 20mA
1% FS
<10 seconds
8 bytes
-10 °C to 45 °C
90 seconds
SG500, SG590, SGM595, CO100A, CO200A, SG810
100
m
1
CSA
mm2
360
x 320
x 135
mm
mm
mm
IP55
3 years from date of manufacture
to 13% (250
) of LEL
ppm)
ppm