Duomo CO200 Manual - Page 2
Browse online or download pdf Manual for Accessories Duomo CO200. Duomo CO200 4 pages.
Overall Dimensions
Fixing 6.5O
80mm
Positioning Sensors
Carbon monoxide has specific gravity of 0.97 and is therefore
slightly lighter than air.
However for positioning purposes, at the concentrations of
carbon monoxide relating to the detector alarm thresholds, the
resultant combination of carbon monoxide and air will neither
rise or fall.
The best position to mount the CO200 Duct is 1.6m above
ground level. The image below shows the suggested position
for the CO200 Duct in a boiler room.
For car parks, 1.6m above ground level is still recommended.
If you require assistance regarding locating sensors please call
our Droitwich factory on (01905) 797989 or fax a drawing of
your application to (01905) 774296 and we will advise
accordingly.
Carbon
Monoxide
60mm
Installing A Sensor
The sensors must be mounted as shown below with
the sintered head pointing vertically down.
Model
CO200
Power Supply
12/24V. dc± 10%
Electrical Input
110mA@13,8V.
Detection
Carbon Monoxide
Sensitivity
from 30 to 300ppm
Important Notes
The installation of this gas detector does not release
the user from observing all the regulations
concerning the characteristics, installation and the
use of gas appliances; the ventilation of the
environment and the elimination of combustion
products in accordance with local recommendations,
regulations and byelaws.
For any damage caused to people, property or
animals resulting from incorrect connection,
installation or application of this gas detector Duomo
will not be held responsible or liable.
Replacing Sensor
When replacing sensors NEVER seperate a sensing
head from the PCB. The sensor has been calibrated
using only that particular board and therefore will not
function correctly with any other.
100mm
Model
CO200
Power Supply
12/24V. dc± 10%
Electrical Input
110mA@13,8V.
Detection
Carbon Monoxide
Sensitivity
from 30 to 300ppm