Technical Specification

Power supply
Power demand
Switching alarm relay
Fault relay
Detection
Sensor
Sensor Element range
Sensor output range
Analog output signal
Detector accuracy
Long term shift in clean air
Response Time
Warm-up time
Time work regime
Functioning humidity
Functioning temperature
USB TestSocket
Compatible Control units
Max. distance between sensor and unit
Cable diameter for connecting sensor
Connection: The sensor connection cables should not be laid with the supply cables. If the cables are laid together with
power cables, you must use a shielded cable
Sensor Enclosure
Size
Degree of protection
INDICATIONS
Regular operation:
Fault:
Main Alarm (Max instant concentration 300 ppm):
TWA (eight hours alarm @ average of 30ppm):
STEL (15 minutes alarm @ 200 ppm):
Precautions and Maintenence
CHECK the integrity of the unit after having removed it from the box.
Check that the data written on the box correspond to the type of gas used.
When doing the electrical connections, follow the drawing closely.
Any use of the detector for purposes other than the intended one is considered improper and as a result of which Duomo
(UK) therefore disclaims any responsibility for possible damages caused to people, animals or objects.
The installation and maintenance of the CO233/A Sensor and removal at the end of the functional life must be carried out
by authorized or specialized personnel.
Do not allow the CO233/A to become wet.
The product is not waterproof either when immersed in water or exposed to high levels of humidity.
13122018.Rev3
CO233/A - Carbon Monoxide Gas Sensor
12 - 24VDC ± 10%
In warm-up 15 mA In Alarm 80 mA max @ 13.8V DC
10 A 250V ~ Resistive 5A 30Vdc resistive SELV
5 A 250V ~ Resistive 5A 30Vdc resistive SELV
Carbon Monoxide (CO)
Electrochemical cell
0-5000 ppm
0-330ppm
4-20 mA standard tolerance
1% FS
< + 2ppm
< 10"
1 to 5 minutes
4 minutes
0-90% non condensed
-20°C to + 50°C
TS1008
BX444-Mc, GS100M, BX150, GS300M, GS300-Mc, BX316xp
100 m
1 mm
Aluminium
100 x 100 x 60mm
IP66