DANLERS CEFLA PIR DALIP Installation Notes - Page 2

Browse online or download pdf Installation Notes for Switch DANLERS CEFLA PIR DALIP. DANLERS CEFLA PIR DALIP 2 pages. Pir occupancy switch with dali dimming

Installation procedure
1. Please read these notes carefully before commencing work.
In case of doubt please consult a qualified electrician.
2. POSITIONING: The CEFLA PIR DALIP should be installed to achieve
correct coverage of the area, see diagram A. Avoid locating this product
where it is exposed to drafty conditions (exposed lobbies, open ceiling
voids or near fans) or near heat sources.
3. Make sure the power is isolated from the circuit.
The PIR should be connected as shown in diagram E:
Thick wire
Brown
L
Live in
Blue
N
Neutral in
Black
SL
Switched Line out
White
SW
Switch / Input
1
Start-up mode
When the PIR is powered up, it will switch on the load for 1 minute, the
load will then switch off and the PIR will enter its Operating Mode.
Time / Run-on / Lux set up
The LUX adjuster spindle on the side of the PIR is used to regulate the
automatic daylight linked dimming function lux level (see diagram D
opposite). This should be adjusted in situ by rotating the LUX adjuster
slowly anticlockwise
(+ to -) so that the desired level of brightness is achieved under the
luminarie(s) being controlled.
If the LUX spindle is quickly turned the lights can be dimmed up and down
to the required LUX level by further rotation of the LUX spindle. Once the
correct level is achieved and there has been no further adjustment to the
LUX spindle,
CEFLA PIR DALIP
the automatic closed loop control will start.
CEFLA PIR DALIP incorporates a fixed 20 second fade rate from maximum
to the set back level.
Sensitivity
CEFLA PIR DALIP incorporates a sensitivity adjuster, labelled 'SENS', to
reduce the range of detection from 100% to 50% in 9 steps
C opposite).
Thin wire (DALI control lines)
Red / Blue Polarity independant
will go through a 30 second delay before
(see diagram
A: Detection diagram
Clearance hole
63 or 64mm (2.5") diameter
B: Detection diagram
For optimum coverage
recommended mounting
height: 2.4 to 5m
up to 5m
up to 7m
C: Adjusting SENSITIVITY and TIME
Typical settings
max
min
max
min
SENS
TIME
50%
100%
40m
20m
10m
40s
5m
80s
2.5m
E: Wiring diagram,
CEFLA PIR DALIP controlling several DALI dimmable ballasts
L
230 VAC
N
Mains
rated
retractive
Optional
wall switch
other load
or rocker
wall switch
(toggled)
Springs can either be left closed (down
the side of the product) or opened out.
Strong detection zone
i.e. person moving arm
or walking towards PIR
Secondary detection zone
i.e. person walking
perpendicular to PIR
D: Adjusting LUX and RUN-ON
Typical settings
max
min
LUX
10s
INFINITE
20s
30m
20m
DALI
Ballast
DALI Control Lines
L
SW
CEFLA PIR DALIP
1
N
SL
max
min
RUN ON
0s
1m
2m
15m
5m
10m
DALI
Ballast