DANLERS ControlZAPP CZ CEFL Installation Notes

Browse online or download pdf Installation Notes for Switch DANLERS ControlZAPP CZ CEFL. DANLERS ControlZAPP CZ CEFL 2 pages. Ceiling flush mounted switch

Variants
DANLERS design and manufacture other ControlZAPP CZCEFLP variants, coded
by the following order codes:
CZ CEFL
Suitable for mains switching
CZ CEFL VF
Suitable for mains switching, Volt Free contacts
CZ CEFL 10VDC
Suitable for 1-10VDC ballasts
CZ CEFL 10VDC VF
Suitable for 1-10VDC ballasts, Volt Free contacts
CZ CEFL DALI
Suitable for DALI ballasts.
Troubleshooting
The output will not switch on:
• The LUX setting as specified by the ControlZAPP App is set too low and is
inhibiting the switch.
• The moving body is not emitting more IR than the background.
(Person wearing insulating clothing in a warm environment)
• Person is too far from the PIR switch, see detection diagram.
• Person is moving unusually slowly (perhaps when testing).
• The control unit battery is not engaged (ON).
Switch RED dip switch next to the telejack connector on the control
unit to the DOWN position.
The output switches on when nobody is present:
• Heater causing infra-red variations in a small cold room.
Resite the CZ CEFL DALI VF control away from heater.
• Please contact DANLERS for further technical support.
Precautions and Warranty
This product conforms to BS EN 60669-2-1, BS EN 55015 and BS EN 60730.
Please ensure the most recent edition of the appropriate local wiring regulations are observed
and suitable protection is provided (protected with the appropriate MCB) 1kV over voltage.
Please ensure that this device is disconnected from the supply if an insulation test is made.
This product is covered by a warranty which extends to 5 years from the date of manufacture.
Products available from DANLERS
• PIR occupancy switches • Daylight linked dimmers • Manual high frequency dimmers
• Photocells • Radio remote controls • Time lag switches • Outdoor security switches
• Dimmers • Heating, ventilation and air-conditioning controls • Bespoke / O.E.M. products
Please call for more information or a free catalogue, or visit our website.
DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK.
Telephone: +44 (0)1249 443377 Fax: +44 (0)1249 443388
Web: www.danlers.co.uk
Company Registered Number 2570169 VAT Registration Number 543 5491 38
08/09/16
INS013 CZ CEFL DALI VF
ControlZAPP Ceiling flush mounted switch
CZ CEFL DALI VF
ControlZAPP ceiling flush passive infra-red switches (PIR) can be flush mounted
into suspended and plasterboard ceilings (diagram A).
These PIR switches incorporate a passive infra-red quad sensor to detect
movement of a warm body within their detection zone (diagram B) and a photocell
to monitor the ambient light level.
ALL adjustments are made via a freely downloadable ControlZAPP App
available from the DANLERS website.
If CZ CEFL DALI VF is set as PIR with LUX input, upon detecting movement, if
the ambient light is dark enough, the ControlZAPP device will turn the output ON.
The ambient threshold can be set to between approximately 30 lux to 1000 lux
and infinite lux (photocell inactive) via the 'Respond to Daylight' settings on the
ControlZAPP App.
If no more movement is detected within a pre-selected time as determined by the
ControlZAPP App, then the ControlZAPP device will turn the output off. This 'Time
Off Timeout' or time lag can be set via the ControlZAPP App adjuster between
10sec and 23hrs 59min 59sec.
Loading /Output
CZ CEFL DALI VF is suitable for switching and dimming DALI ballasts (broadcast
only). CZ CEFL DALI VF can control up to 40mA, eg. 20 ballasts at 2mA (varies
according to make and model of ballasts).
IMPORTANT: To control DALI ballasts you will require a DALI Power Supply Unit.
Please refer to your ballast instructions.
DANLERS DALI Power Supply Unit (order code DALIPSU) is rated at 40mA (DALI
standard allows 250mA maximum). The controls interface of a DALI ballast normally
sources at 2mA.
CZ CEFL DALI VF can also switch up to:
• 10 amps (3000W) of resistive loads
• 6 amps (1500W) fluorescent lamps, high frequency or switch start,
incandescent or mains halogen lamps (recommended with integral safety fuse)
• 3 amps (750W) of electronic or wire wound transformers.
• 2 amps (500W) of low energy lamps: CFL, LED, 2D etc.
• 1 amp (250W) of fans or most metal halide lamps.
Start-up mode and Default settings
When the CZ CEFL DALI VF is powered up, it will take 1 minute for the circuitry to
stabilise (detection LED flashing) and ensure the output is off, the CZ CEFL DALI
VF will then enter its Default Operating Mode.
Please Note: When in the Default Operating Mode the CZ CEFL DALI VF is set up
as an occupancy switch with a 20 minute turn OFF timeout (time lag) and photocell
disabled.
Installation notes
(with volt free output)