DANLERS ControlZAPP CZ CEFL DALI Installation Notes - Page 2

Browse online or download pdf Installation Notes for Switch DANLERS ControlZAPP CZ CEFL DALI. DANLERS ControlZAPP CZ CEFL DALI 2 pages. Ceiling flush mounted switch
Also for DANLERS ControlZAPP CZ CEFL DALI: Installation Notes (2 pages)

DANLERS ControlZAPP CZ CEFL DALI Installation Notes
Installation procedure
1. Please read these notes carefully before commencing work. In case of doubt
please consult a qualified electrician. Ensure wires and cables are securely held
within the connection terminals.
IMPORTANT: The CZ CEFL DALI Control Unit clock battery must be engaged
(ON) prior to installation by switching the RED dip switch (see diagram D) to
the DOWN position.
2. POSITIONING: The CZ CEFL DALI switch should be installed to achieve correct
coverage of the area, see diagram B. If the photocell override facility (enabled via
ControlZAPP app) is required, the switch must be located above an area where
daylight can give greater illumination than the artificial light. Avoid locating this
product where it is exposed to drafty conditions (exposed lobbies, open ceiling
voids or near fans) or near heat sources. To cover large areas PIRs should be
spaced in a 5 metre grid formation.
3. Disconnect the ControlZAPP device from the circuit before performing insulation
testing of the wiring circuit.
4. Do not connect on a circuit with large inductive loads, as induced spikes may
cause false triggering or damage the device.
5. CZ CEFL DALI must be connected to its ControlZAPP Power Supply via the
ControlZAPP communication cable provided, for wiring see diagram C.
NOTE: The use of non ControlZAPP connectors may damage the CZ CEFL DALI
device and will invalidate the warranty.
Settings and calibration
NOTE: ALL settings are adjusted by ControlZAPP App as specified in the
ControlZAPP App User Guide (downloadable from the DANLERS website)
including: MODE settings, SCHEDULER settings and photocell settings and
intelligent photocell calibration procedure.
MODE settings include: Detect Movement (enable or disable), Sensitivity, Short
Visit Mode (with timer), Turn ON automatically (Presence detection or Absence
detection), Turn OFF timeout (from10sec to 23hrs 59min 59sec), Respond to
Daylight (enabled or disabled) the calibration process must be run for the intelligent
photocell to work. Delay before ON or Delay before OFF timers, Scene Recall (ON
or OFF).
SCHEDULER settings include:
DAY TYPES (defining times for each of the different Modes to occur).
WEEKLY SCHEDULE (defining which Day Types are assigned to different days of
the week).
EXCEPTIONS (defining exceptions to the schedule such as holidays).
VIEW ON CALENDAR (overview of schedule).
A: Mounting diagram
CEILING VOID
(At least 78mm deep)
75mm circular hole
cut for PIR switch
B: Detection diagram
Strong detection zone
i.e. person moving arm
or walking towards PIR
up to 5m
up to 7m
C: Wiring diagram
L
100 - 260VAC 50/60Hz
N
DALI Power
Supply Unit*
DALI Control Lines
Optional
L
other load
N
D: Connector diagram
IMPORTANT
Red dip switch (MUST be
switched DOWN (towards lens)
SL
to engage clock battery ON)
L
L
Power Supply
N
DA
DA
For optimum coverage
recommended
mounting height: 2.4 to 5m
Secondary detection
zone i.e. person
walking perpendicular
to PIR
DALI
DALI
Ballast
Ballast
ControlZAPP device
CZ CEFL DALI
SL
*DANLERS Order code: DBPSU
Control Unit
Telejack connector