Consilium Salwico MCP-C WP Manual - Page 11

Browse online or download pdf Manual for Fire Alarms Consilium Salwico MCP-C WP. Consilium Salwico MCP-C WP 15 pages. Manual call point ip67

Consilium Salwico MCP-C WP Manual
DATA S H E ET

Installation

For featured wiring the detector is installed on a
base, provided in IP65 proof version.
The detector is connected to the base through a
fast bayonet clutching and a flying connector.
Certain factors need to be considered when
designing an installation:
• The sensors should be mounted so that
objects do not block their field-of-view (FOV).
This includes glass, Plexiglas and other visibly
transparent materials. Contact Consilium for
more information.
• Whenever possible, sensors should be
mounted so their ranges and fields-of-view
overlap.
• Sensors should be mounted so their FOV
cannot be choppered by moving machinery or
human operators during normal operations
within the area. Therefore they should be
installed as high as possible or on the ceiling.
• Detector window should not be exposed to
hot or cold intermittent airflow which could
change the temperature of the detector itself
or detector FOV background.
• To ensure optimum sensitivity and
performance, sensors should be mounted so
they do not look at hot surfaces: if this is
necessary first follow procedure to ensure no
chopper is present.
• The sensors should be mounted so that they
are easily and safely accessible for inspection
and maintenance.
• If mechanical, high-temperature damage, or
window contamination is likely to occur in the
installed location, then the sensor should be
protected. However the protection method
cannot obstruct the sensors FOV with any
material, including visibly transparent materials,
such as glass and Plexiglas.
• The sensor can be mounted in any
orientation, as long as captive screws are
removed or can be removed.
• Mounting the sensor so that it points
downwards is recommended as this generally
results in minimal window contamination.
• Care must be taken to avoid that sensor
installation exceeds environmental approvals
such as temperature, shocks, vibrations.
The specifications described herein are subject to change without notice.
• Care must be taken to avoid that sensor
installation exceeds electromagnetic
interference approval: in particular install
detectors in places out-of-reach of personnel
(including contractors and crew members).
• It is important NOT to leave any extra cable
slack when installing this detector.
• Cable shield shall be connected to the ground
on one side only.
• The DIP-Switch Setting recommended by
Consilium is to turn Sw.No.2 ON for the
highest sensitivity. For more details, see
Settings.
For more details, see Flame Detector Installation
manual 5100512.
Hint!
For outdoor mounting: Fit the detector
screws on the base to ensure IP67
Protection Index.
Angle of Reception
Dimensions (mm)
Data sheet no. 5200236-00A_Salwico AC-IR-3Fq_M_EN_2014_E
2(3)
www.consilium.se