8. Choosing a position in a room
The SLPIR controller should be fixed to the wall or ceiling. If installed on the wall it should be positioned at 1.5 metres
from the floor pointing towards the detection area. If mounted on the ceiling the orientation to achieve the best
detection should be used. Check the detection range section for more details. Avoid areas with a draught, direct
sun or opposite windows. Do not position the controller above or close to the heaters or other heat sources. Damp
areas or areas where the SLPIR can be mechanically damaged should also be avoided. Avoid installing the
controller in areas where there are metal objects between the heater and the controller. These will reduce the RF
range. The RF range in ideal conditions can be up to 20m however this can be reduced when the signal is passing
through walls or other objects. The range can be also affected where the controller is mounted close to power
cables, motors or equipment producing a strong electromagnetic field. If the temperature control feature is used it
is necessary to use one controller for each room or zone.
9. Installation
The controller is designed to fit onto most single gang back boxes. When a metal box is used this must be earthed.
The controller can be powered by either mains 240VAC 50Hz or 12VDC. The power consumption is less than 1W. Do
not connect mains voltage to 12V terminals, this will damage the controller. The maximum size wire that can be
used is 1mm
, this can be twin and earth or standard flex . Do not overtighten the connector screws. Take care not
2
to damage the components when connecting the cables.
WARNING, this controller is not compatible with single gang metal back box with 4 fixing lugs.
10. Connection to the Main Supply
For the mains power, connect Line and Neutral wires to the connectors marked L and N.
Electrical installation should be carried out by a competent installer, preferably registered with NICEIC (National
Inspection Council for Electrical Installation Contracting) in accordance with the 18
Regulations, (BS.7671), and any relevant Local Authority Bye-Laws.
11. Connection to 12V DC
Powering the controller with 12VDC allows the controller to be installed in a zone 2 area, however, the installation
must comply with the Separated Extra Low Voltage (SELV) requirements. When powered by 12VDC, please ensure
that the power supply is suitable for 12V 0.1A. For 12VDC power connect the positive wire to the terminal marked
+12V and negative to terminal marked –12V.
-
12V DC
+
12. Pairing
In order to pair your heater with the controller :
 Isolate the controller and heater from the power
 Follow the sequence below
 Power ON the controller or controller and heater together
 Wait 2 seconds
 Power OFF the controller or controller and heater together
 Wait 2 seconds
 Power ON the controller or controller and heater together
 Wait 2 seconds
 Power OFF the controller or controller and heater together
 Wait 2 seconds
 Power ON the heater
 Power ON the controller
 If the sequence was followed correctly, the 4 light segments will flash yellow to indicate pairing
 After the pairing is finished, the light segments will change to green.
 If the pairing was successful, the appliance should emit heat. It can take up to 4 seconds.
 After the light segments stop flashing the controller is in the test walk mode to allow testing of the functions. In this
mode the time delay is automatically set to 10 seconds.
 In order to enter normal operation mode turn power to the controller OFF for 2 seconds and back ON.
edition of the IEE Wiring
th
L
Mains Connection
230/240V AC 50Hz
N