Replacing RH/T sensor (en)
Applies for the following products with serial no. lower than:
•
CDP/CDF 40: 1809131526904
•
CDP/CDF 50: 1809241528179
•
CDP/CDF 70: 1810031531072
1.
Remove the front of the unit.
Remove the PPI filter and replace with new as
per partslist.
The new PPI filter must be right up against both
ends of the cabinet.
Make sure that the hole is furthest away from the
front as shown.
Note: For CDP/CDF 40 and 50 the filters
must be cut according to this illustra-
tion.
2.
Release humidity sensor from drip tray
and retract it back in to the compressor
compartment.
In the compressor compartment pull the sensor
through the rear hole in the bottom plate.
3.
Find the compressor compartment cover with
the pre-mounted bracket for the humidity
sensor.
Dismount the old cover.
Mount the new cover and move the sensor to
the front.
200mm
130mm
0mm
1237mm
Note: The bracket is
mounted off center
to fit the hole in the
PPI filter
1447mm