Dantherm 4000 Series Service Manual - Page 12

Browse online or download pdf Service Manual for Air Conditioner Dantherm 4000 Series. Dantherm 4000 Series 17 pages.

Technical data

Introduction
These units are designed for high reliability and electrical efficiency.
Compressor is a rotary type with high efficiency.
Radial fans with backward curved impellers.
Slim MPE Condenser for high performance thus low pressure drop.
4000 btu . units
This table shows the technical data for 4000 BTU models.
Specification
Unit dimensions
(height×width×depth)
Weight
Operational temperature range
Storage temperature / humidity
Noise level, outside 2m distance at
80.6°F. internal / 95°F. Ambient
IP protection EN 60529
Outdoor Enclosure acc. UL 50
Refrigerant type / amount
Cooling capacity at 80.6°F
internal/95°F Ambient (total)
EER Air conditioning at 95°F internal /
95°F Ambient
Internal airflow
External airflow
Input voltage range
Frequency
Power consumption
Circulation / Air Conditioning
Power consumption Heater
LRA (locked rotor current)*
Extension cord dimension
*Recommended over current protection specification to be found on page 5
22
Unit
115 VAC units
230 VAC units
Inch.
29 x 17.3 x 11.3
lbs.
70
°F
-40-+131
°F /RH%
-40-+176 / 0-99
dB(A)
65
IP class
65
Type 3R
Type/lbs
R134a /210g
BTU/h
4092
BTU/h
5.2
CFM
679
CFM
798
VAC
115 +/-10%
230 +/-10%
Hz
60
50/60
W
48/740
W
1000
1000
A
37*
17*
awg
14
14

Electrical schematics

Overall controller
This illustration shows the complete controller connections, internal as well as external:
3: Supply GND
J2
2: NC
Supply
1: Supply 12V
8: Evap out sens GND
7: Evap out sens signal
6: Evap in sens GND
Temp sensors
5: Evap in sens signal
J7
NTC -30 to 85°C
4: Cond sens GND
(-22 to 185°F)
3: Cond sens signal
2: Ret. Sens GND
1: Ret. Sens signal
4: Voltage sensor
3: Voltage sensor
J4
Power sensors
2: Current sensor
1: Current sensor
6: +12V
5: +12V
4: \B
J1
Valve
3: \A
2: B
1: A
6: Cond fan relay out.
5: Cond fan relay 12V
4: Heater relay out.
J5
Relay drive out
3: Heater relay 12V
0/12V DC 200mA
2: Compressor relay out
1: Compressor relay 12V
4: GND
3: Tacho
J11
Fan 1
2: PWM
1: NC
4: GND
3: Tacho
J16
2: PWM
Fan 2
1: NC
3: GND
J22
2: Tacho
Fan 3
1: PWM
Accessory
SD
TTL
TTL interface
(galvanic isolated)
Standard shielded ethernet
cable (568A termination)
1=Gnd
2=B
3=Gnd
RS 485
4=A
5-6=12v line pwr
7-8=line pwr gnd
External
9: Hotspot sens GND
NTC -30 to 85°C
interfaces
(-22 to 185°F)
8: Hotspot sens.
7: Dig GND
Active low
6: Dig2 input
max 12V DC/10mA
J15
5: Dig1 input
AC 1
4: AC1 relay contact
Max. 42 VAC or 60 VDC. /
500mA. Default normally
3: AC1 relay contact
open - jumper changeable
2: Alarm 1 relay contact
Max. 42 VAC or 60 VDC. /
Alarm
500mA. Default normally
1: Alarm 1 relay contact
open - jumper changeable
Fig. 14
23